The chlorine concentration variation in Baghdad water networks was studied. The
chlorine data were collected from Mayoralty of Baghdad and Ministry of Environment
(MOE) for the networks for both sides of the city Karkh and Rasafa for (2008-2009). The
study of these data indicates that there are no systematic testing program .Classified GIS
maps showed that the areas far from the treatment plants have almost always low
chlorine concentration .This indicates that the problem of the low chlorine concentration
in the far areas is due to cracks of pipe along the conveyance path ,as expected. The area's
most frequently have low concentration are Al-sadir,Al-Kadhimya, and Al-Amiria . It
was found also that the chlorine concentrations were lowest in summer months than those
in winter months.The Amiria area district (636) was selected as a case study to test the
ability of using the quantitative- qualitative model in the EPANET software, to find the
required onsite chlorine injection point number, locations and dose, so as to raise the
chlorine concentration to the acceptable limits in the other nodes of the network. The
bulk decay coefficient was found to be (-2.212)1/day and the wall coefficients were
found to be between (-0.001)to(-0.9)1/day The main conclusion of this study is that the
onsite injection can improve the chlorine concentration in Baghdad water supply
networks. The EPANET model can be used effectively to obtain the required injection
program for this purpose.
Forward osmosis (FO) process was applied to concentrate the orange juice. FO relies on the driving force generating from osmotic pressure difference that result from concentration difference between the draw solution (DS) and orange juice as feed solution (FS). This driving force makes the water to transport from orange juice across a semi-permeable membrane to the DS without any energy applied. Thermal and pressure-driven dewatering methods are widely used, but they are prohibitively energy intensive and hence, expensive. Effects of various operating conditions on flux have been investigated. Four types of salts were used in the DS, (NaCl, CaCl2, KCl, and MgSO4) as osmotic agent and the experiments were performed at the concentration of
... Show MoreThe determination of manganese (II) using flow injection analysis with chemiluminescence detection was investigated. Mn2+ in sample solutions injected into a carrier stream of sodium bismuthate (NaBiO3) were oxidised to form MnO4- ions which were capable of producing luminescence after reaction with luminol/KOH in a flow cell. The linear range of the system is from 20 to 80 mg/L with a detection limit 8 mg/L. The proposed system is suitable for determination of Mn2+ in steel alloys after dissolution, filtration and dilution at a rate of approximately 60 samples per hour with a relative standard deviation (RSD)1.2%. Statistical comparison between the proposed system and standard spectrophotometric method revealed that there is no signific
... Show MoreBackground: Tap waters play an important role in fulfilling the people needs for drinking and domestic purposes. Contaminate the tap water with different pollutants has become an issue of great concern for 90% of people who are depended on the tap water as the main source of drinking. Pollutants can make their way easily into the delivering pipes which suffer from the leaking resulting in decreasing the quality of water. Objective: Therefore, assess the water quality for drinking purpose by calculating the water quality index is an important tool to ascertain whether the water is suitable for human consumption or not. Methods: In the present work, the water quality of the Al-Salam, western region of Baghdad city, Iraq was investigated for 7
... Show MoreDetergent is one of the pollutants that poses significant threats to ecological systems. Detergents can also dissolve in wastewater and negatively impact the efficiency of wastewater treatment facilities. They are used for a variety of functions, most notably hygiene, and are an integral aspect of human life. This means that there are a variety of routes by which detergent components can reach the environment. In this Study, twenty-three detergent samples from local markets in Baghdad. The aim of this study is to investigate the concentration of heavy metals Cobalt (Co), Chromium (Cr),Lead (Pb),Zinc (Zn), Iron (Fe) and Cadmium (Cd) in some detergents using Atomic Absorption Spectrophotometer. The results of the concentration of heavy elemen
... Show MoreIn this research an Artificial Neural Network (ANN) technique was applied for the prediction of Ryznar Index (RI) of the flowing water from WTPs in Al-Karakh side (left side) in Baghdad city for year 2013. Three models (ANN1, ANN2 and ANN3) have been developed and tested using data from Baghdad Mayoralty (Amanat Baghdad) including drinking water quality for the period 2004 to 2013. The results indicate that it is quite possible to use an artificial neural networks in predicting the stability index (RI) with a good degree of accuracy. Where ANN 2 model could be used to predict RI for the effluents from Al-Karakh, Al-Qadisiya and Al-Karama WTPs as the highest correlation coefficient were obtained 92.4, 82.9 and 79.1% respectively. For
... Show MorePersistence of antibiotics in the aquatic environment has raised concerns regarding their potential influence on potable water quality and human health. This study analyzes the presence of antibiotics in potable water from two treatment plants in Baghdad City. The collected samples were separated using a solid-phase extraction method with hydrophilic-lipophilic balance (HLB) cartridge before being analyzed. The detected antibiotics in the raw and finished drinking water were analyzed and assessed using high-performance liquid chromatography (HPLC), with fluorometric detector and UV detector. The results confirmed that different antibiotics including fluoroquinolones and
Evaluation was carried out on the existing furrow irrigation system located in an open agricultural field within Hor Rajabh Township, south of Baghdad, Iraq (latitude: 33°09’ N, longitude: 44°24’ E). Two plots were chosen for comparison: treatment plot T1, which used subsurface water retention technology (SWRT) with a furrow irrigation system. While the treatment plot T2 was done by using a furrow irrigation procedure without SWRT. A comparison between the two treatment plots was carried out to study the efficiency of the applied water on crop yield. In terms of agricultural productivity and water use efficiency, plot T1 outperformed plot T2, according to the study’s final fin