Effect of Mixed Corrosion Inhibitors in Cooling Water System
...Show More Authors

The effect of mixed corrosion inhibitors in cooling system was evaluated by using carbon steel specimens and weight loss analysis. The carbon steel specimens immersed in mixture of sodium phosphate (Na2 HPO4) used as corrosion inhibitor and sodium glocunate (C6 H11 NaO7) as a scale dispersant at different concentrations (20,40, 60, 80 ppm) and at different temperature (25,50,75 and 100)ºC for (1-5) days. The corrosion inhibitors efficiency was calculated by using uninhibited and inhibited water to give 98.1%. The result of these investigations indicate that the corrosion rate decreases with the increase the corrosion inhibitors concentration at 80 ppm and at 100ºC for 5 days, (i.e, corrosion rate= 0.014gmd).    

 

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Wed Dec 30 2009
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Corrosion Inhibition of Aluminum Alloy 5083
...Show More Authors

The corrosion inhibition of aluminum alloy 5083 by an environment friendly compound called (8- Hydroxyquinoline) in
acidic and alkaline solutions of pH (2 and 12) respectively were studied using weight loss and polarization techniques.
Also to examine the main and combined effects of the inhibitor concentration, pH, and contact time using factorial
experimental design. Results show that corrosion rate decreased with increasing both inhibitor concentration and
contact time and increased with increasing pH value. The polarization curves show that 8-hydroxyquinoline is a
cathodic inhibitor

View Publication Preview PDF
Publication Date
Sat Mar 01 2008
Journal Name
Al-khwarizmi Engineering Journal
Effect Of Polar Component(1-Propanol) On The Relative Volatility Of The Binary System N-Hexane - Benzene
...Show More Authors

Vapor-liquid equilibrium data are presented for the binary systems n-hexane - 1-propanol, benzene - 1-propanol and n-hexane – benzene at 760 mm of mercury pressure. In addition ternary data are presented at selected compositions with respect to the 1-propanol in the 1-propanol, benzene, n-hexane system at 760 mmHg. The results indicate the relative volatility of n-hexane relative to benzene increases appreciably with addition of 1-propanol.

View Publication Preview PDF
Publication Date
Wed Mar 10 2021
Journal Name
Baghdad Science Journal
Effect of (1,4) phenylenediamine on the corrosion of lead in 1M hydrochloric acid solution
...Show More Authors

The accelerating effect of 1,4- phenylenediamine (PDA) additions in 1M hydrochloric acid solution at temperature rang (20-60) C° has been studied by weight losses measurement during ranging time (1-260) h and by following the pb2+ concentration in solution after several times by using Atomic absorption spectroscopy (AAS) . The volume of hydrogen gas involving was followed also in presence and absence of (PDA) in the corrosive solution .Accelerating enhanced by adding (NaCl , NaBr , NaI ) was also investigated.

View Publication Preview PDF
Crossref
Publication Date
Sat Sep 23 2023
Journal Name
Sciences Journal Of Physical Education
Individual analysis of kinetic response variables according to the measurement of the H7 system for the best jumping players in the national basketball team 2021
...Show More Authors

The skill scale in most of sport activity monitoring a lot of dynamic behaviours conducted with playing situations that help the excerpt's in sport field to evaluate and put right solutions ,soccer one of games that studies in third stage in college and take skills ,dribbling , passing, shooting these skills helps to execute the plans in game ,the researchers notice that there is no test measure the skills of the game in the beginning of the first semester especially in the method of soccer in physical education college and the problem of the research were by answering the question that is there test connect between one or more that one of skill to measure the ability of students to execute the plans in soccer and the conclusion was the bui

... Show More
View Publication Preview PDF
Publication Date
Thu Jul 01 2021
Journal Name
Chemical Methodologies
Novel Synthesis of Some N-Hydroxy Phthalimide Derivatives with Investigation of Its Corrosion Inhibition for Carbon Steel in HCl Solution
...Show More Authors

In the current study, new derivatives were synthesized by reaction of N-hydroxyphthalimide with chloro acetyl chloride in the presence of Et3N as a base to form 1,3-dioxoisoindolin-2-yl 2-chloroacetate (B1), which in turn enters several reactions with different amines where it interacts with primary amines to give 1,3-dioxoisoindolin-2-yl acetate derivatives (B2-B4) in basic medium, in the same way it interacts with these amines but with adding KNCS to form thiourea derivatives (B5-B7). It also reacts with diamines to give bis(azanediyl) derivatives (compounds B8-B10). The prepared derivatives were diagnosed using infrared FTIR and 1HNMR,13CNMR for some derivatives. Compounds B4, B5 and B9 were measured as corrosion inhibitors the inhibitio

... Show More
View Publication Preview PDF
Clarivate
Publication Date
Sat Oct 29 2022
Journal Name
Current Trends In Geotechnical Engineering And Construction (pp.52-61)
Simulation of Residual Chlorine in Al-Yarmouk Drinking Water System Using WaterGEMS
...Show More Authors

Abstract To ensure that the distribution system has safe drinking water. It is necessary to know the residual chlorine concentrations at various points in the network. A chlorine photometer device was used to measure twenty points taken every day for a week at a selected time in the distribution system. Both pressures and flows in the network were measured using bourdon gauge and Tuf-2000H Handheld Digital ultrasonic flow meters. WaterGEMS CONNECT Edition update one software was used to simulate the flow in the network. The Baghdad water department provided the data about the network, such as the lengths of pipes, the layout of the network, and pipes diameters. The network calibrated consists of 781 pipes of different lengths and 542 juncti

... Show More
Crossref
Publication Date
Wed Jan 01 2020
Journal Name
Transplantation Proceedings
Outcomes of SGLT2 Inhibitors Use in Diabetic Renal Transplant Patients
...Show More Authors

View Publication
Scopus (57)
Crossref (57)
Scopus Clarivate Crossref
Publication Date
Sun Jun 30 2013
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Zinc Element Traces to Inhibit Scale Formation on Cooling Tower and Air Cooler Systems
...Show More Authors

Calcium carbonate is predominantly present in aqueous systems, which is
commonly used in industrial processes. It has inverse solubility characteristics
resulting in the deposition of scale on heat transfer surface. This paper focuses on
developing methods for inhibition of calcium carbonate scale formation in cooling
tower and air cooler system where scaling can cause serious problems, ZnCl 2 and ZnI
2 has been investigated as scale inhibitor on AISI 316 and 304. ZnCl 2 were more
effective than ZnI 2 in both systems, and AISI 316 show more receptivity to the
chlorides salt compared to AISI 304. The inhibitors were more effective in cooling
tower than air cooler system. AISI 316 show more constant inhibition effic

... Show More
View Publication Preview PDF
Publication Date
Mon Jun 30 2003
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Interfacial Rheological Properties of Iraqi Crude Oils Water System
...Show More Authors

View Publication Preview PDF
Publication Date
Thu Dec 01 2011
Journal Name
Journal Of Engineering
THEORETICAL AND EXPERIMENTAL STUDY ON THERMAL PERFORMANCE OF CLOSED WET COOLING TOWER
...Show More Authors

Thermal performance of closed wet cooling tower has been investigated experimentally and theoretically
in this work. The theoretical model based on heat and mass transfer equations and heat and mass transfer balance equations which are established for steady state case. A new small indirect cooling tower was used for conducting experiments. The cooling capacity of cooling tower is 1 kW for an inlet water temperature of 38oC, a water mass velocity 2.3 kg/m2.s and an air wet bulb temperature of 26oC. This study investigates the relationship between saturation efficiency, cooling capacity and coefficient of performance of closed wet cooling tower versus different operating parameters such wet-bulb temperature, variable air-spray water fl