Preferred Language
Articles
/
ijcpe-312
Zinc Element Traces to Inhibit Scale Formation on Cooling Tower and Air Cooler Systems
...Show More Authors

Calcium carbonate is predominantly present in aqueous systems, which is
commonly used in industrial processes. It has inverse solubility characteristics
resulting in the deposition of scale on heat transfer surface. This paper focuses on
developing methods for inhibition of calcium carbonate scale formation in cooling
tower and air cooler system where scaling can cause serious problems, ZnCl 2 and ZnI
2 has been investigated as scale inhibitor on AISI 316 and 304. ZnCl 2 were more
effective than ZnI 2 in both systems, and AISI 316 show more receptivity to the
chlorides salt compared to AISI 304. The inhibitors were more effective in cooling
tower than air cooler system. AISI 316 show more constant inhibition efficiency in
cooling tower with maximum of 95% with ZnCl 2 and 83% with ZnI 2 .

View Publication Preview PDF
Quick Preview PDF
Publication Date
Wed Dec 30 2009
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Monitoring of Evaporated Cooling Tower
...Show More Authors

Thep resent study was conducted for monitoring of the evaporative cooling tower in methanol production plant using digital computer' visuql Basic computer program was used for the monitoring of the performance of the cooling tower. The structure program consists of sub programs and forms to show all the related variabltes such as temperature, flow rate, pressure ...etc, that affect the cooling tower operation and give alarms and important function informition regarding these variables.

View Publication Preview PDF
Publication Date
Thu Dec 01 2011
Journal Name
Journal Of Engineering
THEORETICAL AND EXPERIMENTAL STUDY ON THERMAL PERFORMANCE OF CLOSED WET COOLING TOWER
...Show More Authors

Thermal performance of closed wet cooling tower has been investigated experimentally and theoretically
in this work. The theoretical model based on heat and mass transfer equations and heat and mass transfer balance equations which are established for steady state case. A new small indirect cooling tower was used for conducting experiments. The cooling capacity of cooling tower is 1 kW for an inlet water temperature of 38oC, a water mass velocity 2.3 kg/m2.s and an air wet bulb temperature of 26oC. This study investigates the relationship between saturation efficiency, cooling capacity and coefficient of performance of closed wet cooling tower versus different operating parameters such wet-bulb temperature, variable air-spray water fl

... Show More
View Publication Preview PDF
Crossref
Publication Date
Wed Dec 13 2017
Journal Name
Al-khwarizmi Engineering Journal
Energy and Exergy Analysis on Modified Closed Wet Cooling Tower in Iraq
...Show More Authors

The present study involves experimental analysis of the modified Closed Wet Cooling Tower (CWCT) based on first and second law of thermodynamics, to gain a deeper knowledge in this important field of engineering in Iraq. For this purpose, a prototype of CWCT optimized by added packing under a heat exchanger was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the towers thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of air measured at intermediate points of the heat exchanger and packing. Exergy of water and air were calculated by applying the exergy

... Show More
View Publication Preview PDF
Publication Date
Mon Dec 31 2012
Journal Name
Al-khwarizmi Engineering Journal
Experimental Investigation of Using Evaporative Air Cooler for Winter Air-Conditioning in Baghdad
...Show More Authors

This paper presents an efficient methodology to design modified evaporative air-cooler for winter air-conditioning in Baghdad city as well as using it for summer air-conditioning by adding a heating process after the humidification process. laboratory tests were performed on a direct evaporative cooler (DEC) followed by passing the air on hot water through heat exchanger placed in the coolers air duct exit. The tests were conducted on the 2nd of December /2011 when the ambient temperature was 8.1°C and the relative humidity was  (68%). The air flow rate is assumed to vary between 0.069 to 0.209 kg/s with constant water flow rate of 0.03 kg/s in the heat exchanger. The performance is reported in terms of effectiveness of DEC, satura

... Show More
View Publication Preview PDF
Publication Date
Thu Jun 29 2023
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Effect of Black Carbon and Alumina Nanofluid on Thermal and Dynamic Efficiency in Upward Spraying Cooling Tower
...Show More Authors

In cooling water systems, cooling towers play a critical role in removing heat from the water. Cooling water systems are commonly used in industry to dispose the waste heat. An upward spray cooling water systems was especially designed and investigated in this work. The effect of two nanofluids (Al2O3/ water, black carbon /water) on velocity and temperature distributions along reverse spray cooling tower at various concentrations (0.02, 0.08, 0.1, 0.15, and 0.2 wt.%) were investigated, beside the effect of the inlet water temperature (35 ,40, and 45 ͦ C) and water to air flow ratio (L/G) of 0.5, 0.75, and 1.  The best thermal performance was found when the working solution contained 0.1 wt.% for each of Al2

... Show More
View Publication Preview PDF
Crossref
Publication Date
Thu Oct 01 2020
Journal Name
Journal Of Engineering
Electrocoagulation for Treatment of Simulated Blowdown Water Of Cooling Tower
...Show More Authors

This study investigates the results of electrocoagulation (EC) using aluminum (Al) electrodes as anode and stainless steel (grade 316) as a cathode for removing silica, calcium, and magnesium ions from simulated cooling tower blowdown waters. The simulated water contains (50 mg/l silica, 508 mg/l calcium, and 292 mg/l magnesium). The influence of different experimental parameters, such as current density (0.5, 1, and 2 mA/cm2), initial pH(5,7, and 10), the temperature of the simulated solution(250C and 35 0C), and electrolysis time was studied. The highest removal efficiency of 80.183%, 99.21%, and 98.06% for calcium, silica, and magnesium ions, respectively, were obtained at a current de

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Wed Jan 01 2020
Journal Name
Aip Conference Proceedings
Investigation hydraulic performance of splash fills packing in cooling tower
...Show More Authors

Heat is one of the most energy forms emitted to atmosphere by industrial processes. Water is considered to be the best material to reduce heat energy since its available in nature in abundance and has the ability to absorb heat efficiently. Cooling towers are ideal alternatives to re-cool hot water instead of throwing it especially in places that lack natural water resources or when there are environmental precautions because water with high temperature would be harmful to the ecosystem when it recycled to natural resources such as rivers and lakes. Also, cooling towers considered economically feasible when using west water. This paper interests with hydraulic characteristics of a counter flow wet cooling tower which was investigated experi

... Show More
View Publication
Scopus (5)
Crossref (3)
Scopus Crossref
Publication Date
Fri Jan 01 2016
Journal Name
Journal Of Engineering
Thermal Characteristics of Closed Wet Cooling Tower Using Different Heat Exchanger Tubes Arrangement
...Show More Authors

This paper presents thermal characteristics analysis of a modified Closed Wet Cooling Tower (CWCT) based on heat and mass transfer principles to improve the performance of this tower in Iraq. A prototype of CWCT optimized by added packing was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of the air measured at intermediate points of the heat exchanger and packing. Heat exchangers consist of four rows and eight columns for an inline tubes arrangement and six rows and five columns f

... Show More
View Publication Preview PDF
Publication Date
Sat Mar 28 2020
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Different Electrodes Connections in Electrocoagulation of Synthetic Blow down Water of Cooling Tower
...Show More Authors

In this research, the performance of electrocoagulation (EC) using aluminum (Al) electrodes with   Monopolar- parallel (MP-P), and bipolar - series (BP-S) arrangement for simultaneous removal of dissolved silica, and hardness ions (calcium, and magnesium) from synthetic blowdown water of cooling tower were investigated. The effects of current density, initial pH and time of electrolysis on the removal efficiency were studied in a batch stirred unit to find out the best-operating conditions. The obtained results for each target species are evidence that BP-S approach is the best for both electrodes configuration operated at a Current density of 1mA/cm2 through 30 min of treatment and pH=10 with the removal of

... Show More
View Publication Preview PDF
Crossref (4)
Crossref
Publication Date
Sat Jul 22 2023
Journal Name
Journal Of Engineering
Experimental Investigation into the Heat and Mass Transfer in an Indirect Contact Closed Circuit Cooling Tower
...Show More Authors

The heat and mass transfer coefficients of the indirect contact closed circuit cooling tower, ICCCCT, were investigated experimentally. Different experiments were conducted involving the controlling parameters such as air velocity, spray water to air mass flow rate ratio, spray water flow rate, ambient air wet bulb temperature and the provided heat load to investigate their effects on the performance of the ICCCCT. Also the effect of using packing on the performance of the ICCCCT was investigated. It was noticed that these parameters affect the tower performance and the use of packing materials is a good approach to enhance the performance for different operational conditions. Correlations for mass and heat transfer coefficients are pres

... Show More
View Publication Preview PDF
Crossref