Preferred Language
Articles
/
ijcpe-312
Zinc Element Traces to Inhibit Scale Formation on Cooling Tower and Air Cooler Systems
...Show More Authors

Calcium carbonate is predominantly present in aqueous systems, which is
commonly used in industrial processes. It has inverse solubility characteristics
resulting in the deposition of scale on heat transfer surface. This paper focuses on
developing methods for inhibition of calcium carbonate scale formation in cooling
tower and air cooler system where scaling can cause serious problems, ZnCl 2 and ZnI
2 has been investigated as scale inhibitor on AISI 316 and 304. ZnCl 2 were more
effective than ZnI 2 in both systems, and AISI 316 show more receptivity to the
chlorides salt compared to AISI 304. The inhibitors were more effective in cooling
tower than air cooler system. AISI 316 show more constant inhibition efficiency in
cooling tower with maximum of 95% with ZnCl 2 and 83% with ZnI 2 .

View Publication Preview PDF
Quick Preview PDF
Publication Date
Wed Dec 25 2019
Journal Name
Journal Of Engineering
Corrosion Rate Optimization of Mild-Steel under Different Cooling Tower Working Parameters Using Taguchi Design
...Show More Authors

This study investigates the implementation of Taguchi design in the estimation of minimum corrosion rate of mild-steel in cooling tower that uses saline solution of different concentration. The experiments were set on the basis of Taguchi’s L16 orthogonal array. The runs were carried out under different condition such as inlet concentration of saline solution, temperature, and flowrate. The Signal-to- Noise ratio and ANOVA analysis were used to define the impact of cooling tower working conditions on the corrosion rate. A regression had been modelled and optimized to identify the optimum level for the working parameters that had been founded to be 13%NaCl, 35ᴼC, and 1 l/min. Also a confirmation run to establish the p

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Sun Jan 01 2017
Journal Name
Journal Of Engineering
Performance Enhancement of an Air Cooled Air Conditioner with Evaporative Water Mist Pre-cooling
...Show More Authors

The present paper deals with experimental investigation of the performance of air cooled split air conditioner, with evaporative water mist pre cooling to increase the cooling capacity and reduce the consumption power under hot and dry climate. This investigation considers how the performance can be enhanced by using water mist to pre-cool ambient air entering the condensers by adiabatic cooling process which depends on the ambient air wet bulb temperature; as well the condensing temperature and condensing pressure will be decreased accordingly. So the cooling capacity would be increased and consumption power would be decreased, consequently the energy ratio, EER would be improved. The performance of air cooled air conditioner with water

... Show More
View Publication Preview PDF
Publication Date
Sat Aug 01 2015
Journal Name
Journal Of Engineering
An Investigation into Thermal Performance of Closed Wet Cooling Tower for Use with Chilled Ceilings in Buildings
...Show More Authors

Chilled ceilings systems offer potential for overall capital savings. The main aim of the present research is to investigate the thermal performance of the indirect contact closed circuit cooling tower, ICCCCT used with chilled ceiling, to gain a deeper knowledge in this important field of engineering which has been traditionally used in various industrial & HVAC systems. To achieve this study, experimental work were implemented for the ICCCCT use with chilled ceiling. In this study the thermal performances of closed wet cooling tower use with chilled ceiling is experimentally and theoretically investigated. Different experimental tests were conducted by varying the controlling parameters to investigate their effects

... Show More
View Publication Preview PDF
Publication Date
Sat Jan 01 2022
Journal Name
Thermal Science
Experimental investigation of the thermal performance of wet cooling tower with splash fills packing
...Show More Authors

With the increasing intensity of the ecological and environmental problems and the scarcity of fresh water, this paper was introduced to investigate the ability to use treated wastewater as a cooling media via studying its behavior throughout a cooling tower. The simultaneous transfer of heat and mass from the treated wastewater to air over splash-fill packing arranged in a zigzag manner was studied. The characteristic of the cooling tower, the outlet water temperature, and the rejected heat were investigated as the water-to-air ratio and inlet water temperature were varied. The core results show that the cooling tower of the tower decreases with increasing water-to-air ratio, and increases with the raise of inlet water temperature.

... Show More
View Publication
Scopus (6)
Crossref (6)
Scopus Clarivate Crossref
Publication Date
Fri Jun 01 2012
Journal Name
Journal Of Economics And Administrative Sciences
The Probability of Implementation Some Rules of Process Organization –Study of the Production Air-cooler engines
...Show More Authors

This research is Interested in how the performance and implementation of factory production engine coolants of the General Company for Electrical Industries of its work, and to facilitate the flow of the decisions of senior management and access to all configurations, to ensure differentiation desired and reduce lost sales, resulting from poor scheduling of operations through the application of certain rules of scheduling operations in the production plant Engines Air-cooler, the objectives of research in identifying the best base and working to reduce the time and cost of Same Rules of Process which are considered the most influential of any organization and thr

... Show More
View Publication Preview PDF
Crossref
Publication Date
Fri Mar 31 2017
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Investigation Desulfurization Method Using Air and Zinc Oxide/Activated Carbon Composite
...Show More Authors

In present work examined the oxidation desulfurization in batch system for model fuels with 2250 ppm sulfur content using air as the oxidant and ZnO/AC composite prepared by thermal co-precipitation method. Different factors were studied such as composite loading 1, 1.5 and 2.5 g, temperature 25 oC, 30 oC and 40 oC and reaction time 30, 45 and 60 minutes. The optimum condition is obtained by using Tauguchi experiential design for oxidation desulfurization of model fuel. the highest percent sulfur removal is about 33 at optimum conditions. The kinetic and effect of internal mass transfer were studied for oxidation desulfurization of model fuel, also an empirical kinetic model was calculated for model fuels

... Show More
View Publication Preview PDF
Publication Date
Wed Apr 05 2023
Journal Name
Journal Of Engineering
Performance Evaluation of Small Scale Air-Conditioning System Using R22 and Alternative Refrigerants
...Show More Authors

A mathematical model has been formulated to predict the influence of high outdoor air temperature on the performance of small scale air - conditioning system using R22 and alternative refrigerants R290, R407C, R410A. All refrigerants were investigated in the cooling mode operation. The mathematical model results have been validated with experimental data extracted from split type air conditioner of 2 TR capacity. This entailed the construction of an experimental test rig which consists of four main parts. They are, the refrigeration system, psychrometric test facility, measuring instrumentation, and auxiliary systems. The conditioned air was maintained at 25 0C dry bulb and 19 0C wet bulb for all tests. The outdoor ambient air temperatur

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Tue Mar 16 2021
Journal Name
2021 4th International Conference On Energy Conservation And Efficiency (icece)
Finite Element Modeling Of Finned Double-Pass Solar Air Heaters
...Show More Authors

View Publication
Scopus (3)
Crossref (1)
Scopus Clarivate Crossref
Publication Date
Tue Mar 01 2016
Journal Name
Al-academy
Heating and cooling systems in women's clothing stores: سماء فاضل خليل
...Show More Authors

Environmental Control Systems form one of the integral tasks of the designer, resulting from his/her acquaintance with the nature of sites and the way they are deployed to achieve modern space entity which is witnessing significant development in the field of interior design.Good deployment of these systems offer us, as designers, high potential and several varied solutions to configure internal spaces characterised as a fertile field of study and knowledge.The research problem was identified in the marginalisation of the importance of Environmental Control Systems as an important designing factor to achieve integrated design. The research problem was demonstrated in Chapter One, along with defining the objectives and formulating

... Show More
View Publication Preview PDF
Crossref
Publication Date
Thu Sep 30 2004
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Control of Calcium Scale and Corrosion of Medical City Cooling Water System using Sulfuric Acid
...Show More Authors

View Publication Preview PDF