Theoretical Prediction of Optimum Chilled Water Distribution Configuration in Air Conditioning Terminal Unit
...Show More Authors

 The distribution of chilled water flow rate in terminal unit is a major factor used to evaluate the performance of central air conditioning unit. In this work, a theoretical chilled water distribution in the terminal units has been studied to predict the optimum heat performance of terminal unit. The central Air-conditioning unit model consists of cooling/ heating coil (three units), chilled water source (chiller), three-way and two-way valve with bypass, piping network, and pump. The term of optimization in terminal unit ingredient has two categories, the first is the uniform of the water flow rate representing in statically permanents standard deviation (minimum value) and the second category is the maximum heat transfer rate from all terminal units. The hydraulic and energy equations governing the performance of unit solved with the aid of FORTRAN code with considering the following parameters: total water flow rate, chilled water supply temperature, and variable valve opening. It was found that the optimum solution of three-way valve case at 8°C water supply temperature, 0.12 kg/s total water flow rate and valve opening order (valve 1: 100%, valve 2: 100% and valve 3: 75%) with total heat rate (987.92 Watt) and standard deviation (1.181E-3). Also, for the two-way valve case the results showed that the optimum condition at 8°C water supply temperature, 0.12 kg/s total water flow rate and valve opening order (valve 1: 75%, valve 2: 75% and valve 3: 50%) with total heat rate and standard deviation (717Watt) and (5.69E-4) respectively.

Crossref
View Publication Preview PDF
Quick Preview PDF
Publication Date
Sat Jan 01 2022
Journal Name
Journal Of The Mechanical Behavior Of Materials
Concrete strength development by using magnetized water in normal and self-compacted concrete
...Show More Authors
Abstract<p>The main objective of this work was to adopt an environmentally friendly technology with enhanced results. The technology of magnetic water (MW) treatment system can be used in concrete mixture production instead of potable water (PW) to improve both workability and strength. Two types of concrete were adopted: normal concreter production with two grades 25 and 35 MPa and the self-compacted concrete (SCC) with 35 MPa grade. The concrete mixes containing MW instead of PW results showed that, for 25 MPa grade, an improvement in a compressive strength of 15.1, 14.8, and 10.2% was achieved for 7, 28, and 90 days, respectively. For 35 MPa grade, an improvement of 13.6, 11.5, and </p> ... Show More
View Publication
Scopus (3)
Crossref (5)
Scopus Clarivate Crossref
Publication Date
Sat Jan 01 2022
Journal Name
Journal Of The Mechanical Behavior Of Materials
Concrete strength development by using magnetized water in normal and self-compacted concrete
...Show More Authors
Abstract<p>The main objective of this work was to adopt an environmentally friendly technology with enhanced results. The technology of magnetic water (MW) treatment system can be used in concrete mixture production instead of potable water (PW) to improve both workability and strength. Two types of concrete were adopted: normal concreter production with two grades 25 and 35 MPa and the self-compacted concrete (SCC) with 35 MPa grade. The concrete mixes containing MW instead of PW results showed that, for 25 MPa grade, an improvement in a compressive strength of 15.1, 14.8, and 10.2% was achieved for 7, 28, and 90 days, respectively. For 35 MPa grade, an improvement of 13.6, 11.5, and </p> ... Show More
Crossref (5)
Crossref
Publication Date
Wed Aug 05 2015
Journal Name
International Journal Of Current Engineering And Technology
Water Quality Index Assessment using GIS Case study: Tigris River in Baghdad City
...Show More Authors

In this study water quality index (WQI) was calculated to classify the flowing water in the Tigris River in Baghdad city. GIS was used to develop colored water quality maps indicating the classification of the river for drinking water purposes. Water quality parameters including: Turbidity, pH, Alkalinity, Total hardness, Calcium, Magnesium, Iron, Chloride, Sulfate, Nitrite, Nitrate, Ammonia, Orthophosphate and Total dissolved solids were used for WQI determination. These parameters were recorded at the intakes of the WTPs in Baghdad for the period 2004 to 2011. The results from the annual average WQI analysis classified the Tigris River very poor to polluted at the north of Baghdad (Alkarkh WTP) while it was very poor to very polluted in t

... Show More
Publication Date
Wed Jan 01 2025
Journal Name
Aip Conference Proceedings
Biofilm formation rate measurement in water and biomedical systems using photometric smartphones applications
...Show More Authors

View Publication
Scopus Crossref
Publication Date
Sun Jun 07 2009
Journal Name
Baghdad Science Journal
The effect of hot water and ethanol extract of Nigella sativa in immune system of Albino Mice
...Show More Authors

The result showed that hot water and ethanol extracts of Nigella sativa contain alkaloids ,saponins, flavonoids,tannins,glycosides,terpins and steroids. Albino mice were administered orally with 0.1 of the extract at dose of 100 mg/kg, body weight the results showed high level of white blood cell ,total and differential count of WBC,phagocytosis index, mitotic index, Arthus and delayed type hypersensitivity. The result, also showed high level of hemoglobin (Hb) and the packed cell volume (PCV) the alcoholic extract has been found more efficient than hot water extract on mice.

View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Sun Mar 07 2010
Journal Name
Baghdad Science Journal
Effect of magnetic water in the some parameters of growth & activity of some enzymes in the ( Raphanus raphanistrum L.) Plant
...Show More Authors

View Publication Preview PDF
Crossref
Publication Date
Sun Mar 03 2013
Journal Name
Baghdad Science Journal
Effect of Magnetic Water Treatment on Prevention of CaCO3 Scales
...Show More Authors

Permanent magnets of different intensities were used to investigate the effect of a magnetic field in the process of preventing deposits of calcium carbonate. The magnets were fixed on the water line from the tap outside. Then heating a sample of this water in flasks and measuring the amount of sediment in a manner weighted differences. These experiments comprise to the change of the velocity of water flow, which amounted to (0.5, 0.75, 1) m/sec through the magnetic fields that are of magnetic strength (2200, 6000, 9250, 11000) Gauss, and conduct measurements, tests and compare them with those obtained from the use of ordinary water.The results showed the effectiveness of magnetic treatment in reducing the rate of deposition of calcium carb

... Show More
View Publication Preview PDF
Crossref
Publication Date
Tue Feb 28 2017
Journal Name
Journal Of Engineering
Effects of Magnetized Water on the Accumulated Depth of Infiltration
...Show More Authors

This study was carried out to investigate the effects of magnetized water on accumulated infiltration depth. A test rig was designed and constructed for this purpose was installed at the water tests laboratory of the Department of Water Resources Engineering at the University of  aghdad. The investigation was carried out by using two types of soil, different flow velocities throughout magnetizing device and different configuration of magnets over and under the water passage of the magnetizing device. The soils that were used in the experiments are clayey and sandy soils.  Six different flow velocities throughout magnetizing device ranged between 0.29 to 1.19 cm/s and ten configurations of arranging the magnets over and under th

... Show More
View Publication Preview PDF
Publication Date
Tue Apr 20 2021
Journal Name
Journal Of Optical Communications
Analyzing of UVLC system considering the effect of water depth
...Show More Authors
Abstract<p>This paper presents a new approach to discover the effect of depth water for underwater visible light communications (UVLC). The quality of the optical link was investigated with varying water depth under coastal water types. The performance of the UVLC with multiple input–multiple output (MIMO) techniques was examined in terms of bit error rate (BER) and data rate. The theoretical result explains that there is a good performance for UVLC system under coastal water.</p>
View Publication
Scopus (5)
Crossref (5)
Scopus Crossref
Publication Date
Thu Oct 01 2020
Journal Name
Journal Of Engineering
Electrocoagulation for Treatment of Simulated Blowdown Water Of Cooling Tower
...Show More Authors

This study investigates the results of electrocoagulation (EC) using aluminum (Al) electrodes as anode and stainless steel (grade 316) as a cathode for removing silica, calcium, and magnesium ions from simulated cooling tower blowdown waters. The simulated water contains (50 mg/l silica, 508 mg/l calcium, and 292 mg/l magnesium). The influence of different experimental parameters, such as current density (0.5, 1, and 2 mA/cm2), initial pH(5,7, and 10), the temperature of the simulated solution(250C and 35 0C), and electrolysis time was studied. The highest removal efficiency of 80.183%, 99.21%, and 98.06% for calcium, silica, and magnesium ions, respectively, were obtained at a current de

... Show More
View Publication Preview PDF
Crossref (5)
Crossref