Preferred Language
Articles
/
joe-276
Thermal Characteristics of Closed Wet Cooling Tower Using Different Heat Exchanger Tubes Arrangement
...Show More Authors

This paper presents thermal characteristics analysis of a modified Closed Wet Cooling Tower (CWCT) based on heat and mass transfer principles to improve the performance of this tower in Iraq. A prototype of CWCT optimized by added packing was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of the air measured at intermediate points of the heat exchanger and packing. Heat exchangers consist of four rows and eight columns for an inline tubes arrangement and six rows and five columns for staggered tubes arrangement. According to experimental data, the inline tubes arrangement has a better thermal performance than the staggered tubes arrangement. The inline tubes arrangement enhanced thermal efficiency more than (7%) compared to the staggered tubes arrangement. Furthermore the effect of added packing to CWCT on thermal performance was significant compared to CWCT without packing. Comparing CWCT with packing, it has been observed that the best performance for the CWCT with packing under heat exchanger. It can be watched that the thermal efficiency for CWCT with packing under heat exchanger and CWCT with packing above heat exchanger approximately (28%) and (16%) higher than that CWCT without packing respectively. This study provides correlations to predict heat and mass transfer considering the influences of operational parameters for both inline and staggered heat exchanger tubes arrangement.

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Tue Dec 30 2014
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Performance Evaluation of Three Phase Spray Direct Contact Heat Exchanger
...Show More Authors

 

The present investigation deals with experimental study of three-phase direct-contact heat exchanger, for water-Freon R11 system, where water is the continuous phase (liquid) and Freon R11 (liquid-gas) is the dispersed phase. The test section consisted of a cylindrical Perspex column with inner diameter 8cm and 1.2m long, in which, water was to be confined. Liquid Freon R11 drops were injected into the hot water filled column, through a special design of distributors at the bottom of the column. The liquid Freon R11 drops rose on their way up and evaporated into two-phase bubbles at atmospheric pressure. The study was devoted to express the effect of process variables such as c

... Show More
View Publication Preview PDF
Publication Date
Thu Jan 01 2015
Journal Name
Journal Of Engineering
Shell and Double Concentric Tube Heat Exchanger Calculations and Analysis
...Show More Authors

This study concerns a new type of heat exchangers, which is that of shell-and-double concentric tube heat exchangers. The case studies include both design calculations and performance calculations.

       The new heat exchanger design was conducted according to Kern method. The volumetric flow rates were 3.6 m3/h and 7.63 m3/h for the hot oil and water respectively. The experimental parameters studied were: temperature, flow rate of hot oil, flow rate of cold water and pressure drop.

A comparison was made for the theoretical and experimental results and it was found that the percentage error for the hot oil outlet temperature was (- 1.6%). The percentage

... Show More
View Publication
Publication Date
Thu Aug 31 2017
Journal Name
Journal Of Engineering
Study and Analysis of Concentric Shell and Double Tube Heat Exchanger Using - Al 2 O 3 Nanofluid
...Show More Authors

    Heat exchanger is an important device in the industry for cooling or heating process. To increase the efficiency of heat exchanger, nanofluids are used to enhance the convective heat . transfer relative to the base fluid. - Al2O3/water nanofluid is used as cold stream in the shell and double concentric tube heat exchanger counter current to the hot stream basis oil. These nanoparticles were of particle size of 40 nm and it was mixed with a base fluid (water) at volume
concentrations of 0.002% and 0.004%. The results showed that each of Nusselt number and overall heat transfer coefficient increased as nanofluid concentrations increased. The pressure drop of nanofluid increased slightly than the base fluid because

... Show More
View Publication Preview PDF
Publication Date
Tue Mar 30 2010
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
PC-Based Controller for Shell and Tube Heat Exchanger
...Show More Authors

PC-based controller is an approach to control systems with Real-Time parameters by controlling selected manipulating variable to accomplish the objectives. Shell and tube heat exchanger have been identified as process models that are inherently nonlinear and hard to control due to unavailability of the exact models’ descriptions. PC and analogue input output card will be used as the controller that controls the heat exchanger hot stream to the desired temperature.
The control methodology by using four speed pump as manipulating variable to control the temperature of the hot stream to cool to the desired temperature.
In this work, the dynamics of cross flow shell and tube heat exchanger is modeled from step changes in cold water f

... Show More
View Publication Preview PDF
Publication Date
Thu Jan 31 2019
Journal Name
Journal Of Engineering
CFD Application on Shell and Double Concentric Tube Heat Exchanger
...Show More Authors

This work is concerned with the design and performance evaluation of a shell and double concentric tubes heat exchanger using Solid Works and ANSY (Computational Fluid Dynamics).

Computational fluid dynamics technique which is a computer-based analysis is used to simulate the heat exchanger involving fluid flow, heat transfer. CFD resolve the entire heat exchanger in discrete elements to find: (1) the temperature gradients, (2) pressure distribution, and (3) velocity vectors.  The RNG k-ε model of turbulence is used to determining the accurate results from CFD.

The heat exchanger design for this work consisted of a shell and eight double concentric tubes. The number of inlets are three and that of o

... Show More
View Publication Preview PDF
Crossref (2)
Crossref
Publication Date
Sun Dec 31 2017
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Study and Analysis of Concentric Shell and Double Tube Heat Exchanger Using Tio2 Nanofluid
...Show More Authors

In this paper, nanofluid of TiO2/water of concentrations of 0.002% and 0.004% volume was used. This nanofluid was flowing through heat exchanger of shell and concentric double tubes with counter current flow to the hot oil. The thermal conductivity of nanofluid is enhanced with increasing concentrations of the TiO2, this increment was by 19% and 16.5% for 0.004% and 0.002% volume respectively relative to the base fluid (water). Also the heat transfer coefficient of the nanofluid is increased as Reynold's number and nanofluid concentrations increased too. The heat transfer coefficient is increased by 66% and 49% for 0.004% and 0.002% volume respectively relative to the base fluid. This study showed that the friction

... Show More
View Publication Preview PDF
Publication Date
Thu Jan 01 2015
Journal Name
Journal Of Engineering
Experimental Study of the effect of closed cavity wall on buildings cooling loads saving
...Show More Authors

The experimental study showed the use of closed cavity wall (the thickness of the cavity 5cm) made a percentage reduction in the cooling load caused by heat gain from the wall by (21.5 %) compared with the conventional wall. also the thermal resistance of the closed cavity was an average (0.2 m2.oC/W).

The experimental results of the study showed that the use of closed cavity wall reduced the average temperature of the inner surface of the wall during the day, and that the reduction was an average (0.45 oC)  when compared with the conventional wall , as well as the use of closed cavity wall reduced the temperature difference range of the inner surface of the wall during the day, and that the

... Show More
View Publication
Publication Date
Thu Feb 01 2024
Journal Name
Journal Of Energy Storage
A critical review on phase change materials (PCM) based heat exchanger: Different hybrid techniques for the enhancement
...Show More Authors

English

View Publication
Scopus (202)
Crossref (199)
Scopus Crossref
Publication Date
Thu May 18 2023
Journal Name
Journal Of Engineering
Numerical Study Of Heat Transfer In Cooling Passages Of Turbine Blade
...Show More Authors

As the temperature of combustion gases is higher than the melting temperature of the turbine materials, cooling of turbine parts in a gas turbine engine is necessary for safe operation. Cooling methods investigated in this computational study included cooling flow losses. Film-cooling is one typically used cooling method whereby coolant is supplied through holes passage, in present study the holes placed along the camber line of the blade. The subject of this paper is to evaluate the heat transfer that occur on the holes of blade through different
blowing coolant rates. The cases of this study were performed in a low speed wind tunnel with two tip gap at small and large (0.03 and 0.09cm) and multiple coolant flow rates through the fil

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Thu Mar 31 2022
Journal Name
Journal Of The College Of Education For Women
Characteristics of Rainfall in Dry and Wet Seasons in Iraq
...Show More Authors

      This research aims at making a comparative survey between the dry season in (2017-2018) and the wet season (2018-2019) in Iraq concerning the variation of rainfall and pressure systems responsible for such a difference. In this paper, seven climatological stations have been selected: Mosul, Kirkuk, Khanaqin, Baghdad, Rutba, Diwaniyah and Basra. Results have shown that the first category of rainfall of the two seasons has recorded a higher number of rainy days in comparison with the second and third categories with a total of 274 day in a dry season and 403 day of a wet season. Further, the total amount of the annual continuous rain is higher than the total of thunderstorms in a dry season as well as in the

... Show More
View Publication Preview PDF
Crossref