Preferred Language
Articles
/
joe-276
Thermal Characteristics of Closed Wet Cooling Tower Using Different Heat Exchanger Tubes Arrangement
...Show More Authors

This paper presents thermal characteristics analysis of a modified Closed Wet Cooling Tower (CWCT) based on heat and mass transfer principles to improve the performance of this tower in Iraq. A prototype of CWCT optimized by added packing was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of the air measured at intermediate points of the heat exchanger and packing. Heat exchangers consist of four rows and eight columns for an inline tubes arrangement and six rows and five columns for staggered tubes arrangement. According to experimental data, the inline tubes arrangement has a better thermal performance than the staggered tubes arrangement. The inline tubes arrangement enhanced thermal efficiency more than (7%) compared to the staggered tubes arrangement. Furthermore the effect of added packing to CWCT on thermal performance was significant compared to CWCT without packing. Comparing CWCT with packing, it has been observed that the best performance for the CWCT with packing under heat exchanger. It can be watched that the thermal efficiency for CWCT with packing under heat exchanger and CWCT with packing above heat exchanger approximately (28%) and (16%) higher than that CWCT without packing respectively. This study provides correlations to predict heat and mass transfer considering the influences of operational parameters for both inline and staggered heat exchanger tubes arrangement.

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Wed Dec 30 2009
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Monitoring of Evaporated Cooling Tower
...Show More Authors

Thep resent study was conducted for monitoring of the evaporative cooling tower in methanol production plant using digital computer' visuql Basic computer program was used for the monitoring of the performance of the cooling tower. The structure program consists of sub programs and forms to show all the related variabltes such as temperature, flow rate, pressure ...etc, that affect the cooling tower operation and give alarms and important function informition regarding these variables.

View Publication Preview PDF
Publication Date
Fri Mar 01 2019
Journal Name
Al-khwarizmi Engineering Journal
Performance Estimation of Heat Exchanger Operates By Evaporative Cooling Manner
...Show More Authors

        In this study the design and installation of evaporative air cooler was carried out using completely outdoor air (fresh air) according to two stage evaporative cooling principle. The laboratory equipment was installed by designing and manufacturing a cross flow plate heat exchanger, where aluminum plates used for this purpose with dimensions (50 × 30 × 40 cm). The surfaces of heat exchanger were covered by sawdust from wetted channels side, to increase the percentage of wetting these surfaces and hence improve the performance and efficiency of air cooler.

        An experimental study was carried out to estimate the performance of cooling system, where som

... Show More
View Publication Preview PDF
Publication Date
Sat Mar 28 2020
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Different Electrodes Connections in Electrocoagulation of Synthetic Blow down Water of Cooling Tower
...Show More Authors

In this research, the performance of electrocoagulation (EC) using aluminum (Al) electrodes with   Monopolar- parallel (MP-P), and bipolar - series (BP-S) arrangement for simultaneous removal of dissolved silica, and hardness ions (calcium, and magnesium) from synthetic blowdown water of cooling tower were investigated. The effects of current density, initial pH and time of electrolysis on the removal efficiency were studied in a batch stirred unit to find out the best-operating conditions. The obtained results for each target species are evidence that BP-S approach is the best for both electrodes configuration operated at a Current density of 1mA/cm2 through 30 min of treatment and pH=10 with the removal of

... Show More
View Publication Preview PDF
Crossref (4)
Crossref
Publication Date
Thu Jun 29 2023
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Effect of Black Carbon and Alumina Nanofluid on Thermal and Dynamic Efficiency in Upward Spraying Cooling Tower
...Show More Authors

In cooling water systems, cooling towers play a critical role in removing heat from the water. Cooling water systems are commonly used in industry to dispose the waste heat. An upward spray cooling water systems was especially designed and investigated in this work. The effect of two nanofluids (Al2O3/ water, black carbon /water) on velocity and temperature distributions along reverse spray cooling tower at various concentrations (0.02, 0.08, 0.1, 0.15, and 0.2 wt.%) were investigated, beside the effect of the inlet water temperature (35 ,40, and 45 ͦ C) and water to air flow ratio (L/G) of 0.5, 0.75, and 1.  The best thermal performance was found when the working solution contained 0.1 wt.% for each of Al2

... Show More
View Publication Preview PDF
Crossref
Publication Date
Thu Aug 04 2022
Journal Name
Journal Of Nanomaterials
Thermal Management of the Melting Process in a Latent Heat Triplex Tube Storage System Using Different Configurations of Frustum Tubes
...Show More Authors

In this study, the energy charging mechanism is mathematically modeled to determine the impact of design modifications on the thermofluidic behavior of a phase change material (PCM) filled in a triplex tube containment geometry. The surface area of the middle tube, where the PCM is placed, is supported by single or multi-internal frustum tubes in vertical triplex tubes to increase the performance of the heating and cooling of the system. In addition to the ordinary straight triplex tubes, three more scenarios are considered: (1) changing the middle tube to the frustum tube, (2) changing the inner tube to the frustum tube, and (3) changing both the internal and central tubes to the frustum tubes. The impact of adopting the tube desig

... Show More
View Publication
Scopus (38)
Crossref (26)
Scopus Clarivate Crossref
Publication Date
Sun Nov 01 2015
Journal Name
Journal Of Engineering
Heat Transfer Characteristics of a Fluid Flow in Multi Tube Heat Exchanger Fitted with Perforated Fins
...Show More Authors

The heat transfer and flow resistance characteristics for air flow cross over circular finned tube heat exchanger has been studied numerically and experimentally. The purpose of the study was to improve the heat transfer characteristics of an annular finned-tube heat exchanger for better performance. The study has concentrated on the effect of the number of perforations and perforations shapes on the heat transfer and pressure drop across a staggered finned tube heat exchanger. The Numerical part of present study has been performed using ANSYS Fluent 14.5 using SST Turbulent model, while the experimental study consist from a test rig with different models of heat exchangers and all required measurement devices were build

... Show More
View Publication Preview PDF
Publication Date
Fri Apr 01 2016
Journal Name
Journal Of Engineering
Numerical Study of Heat Transfer Enhancement in Heat Exchanger Using AL2O3 Nanofluids
...Show More Authors

In this study, the flow and heat transfer characteristics of Al2O3-water nanofluids for a range of the Reynolds number of 3000, 4500, 6000 and 7500 with a range of volume concentration of 1%, 2%, 3% and 4% are studied numerically. The test rig consists of cold liquid loop, hot liquid loop and the test section which is counter flow double pipe heat exchanger with 1m length. The inner tube is made of smooth copper with diameter of 15mm. The outer tube is made of smooth copper with diameter of 50mm. The hot liquid flows through the outer tube and the cold liquid (or nanofluid) flow through the inner tube. The boundary condition of this study is thermally insulated the outer wall with uniform velocity a

... Show More
View Publication Preview PDF
Publication Date
Tue Nov 09 2021
Journal Name
Energies
Natural Convection Effect on Solidification Enhancement in a Multi-Tube Latent Heat Storage System: Effect of Tubes’ Arrangement
...Show More Authors

The solidification process in a multi-tube latent heat energy system is affected by the natural convection and the arrangement of heat exchanger tubes, which changes the buoyancy effect as well. In the current work, the effect of the arrangement of the tubes in a multi-tube heat exchanger was examined during the solidification process with the focus on the natural convection effects inside the phase change material (PCM). The behavior of the system was numerically analyzed using liquid fraction and energy released, as well as temperature, velocity and streamline profiles for different studied cases. The arrangement of the tubes, considering seven pipes in the symmetrical condition, are assumed at different positions in the system, i

... Show More
View Publication
Scopus (13)
Crossref (12)
Scopus Clarivate Crossref
Publication Date
Tue Sep 15 2020
Journal Name
International Journal Of Energy Research
Effect of airflow channel arrangement on the discharge of a composite metal foam‐phase change material heat exchanger
...Show More Authors

View Publication
Scopus (41)
Crossref (36)
Scopus Clarivate Crossref
Publication Date
Wed Jul 31 2019
Journal Name
Journal Of Engineering
Enhancing Heat Transfer in Tube Heat Exchanger by Inserting Discrete Twisting Tapes with Different Positions
...Show More Authors

Enhancement of heat transfer in the tube heat exchanger is studied experimentally by using discrete twisted tapes. Three different positions were selected for inserting turbulators along tube section (horizontal position by α= 00, inclined position by α= 45 0 and vertical position by α= 900). The space between turbulators was fixed by distributing 5 pieces of these turbulators with pitch ratio    PR = (0.44). Also, the factor of constant heat flux was applied as a boundary condition around the tube test section for all experiments of this investigation, while the flow rates were selected as a variable factor (Reynolds number values vary from 5000 to 15000). The results s

... Show More
View Publication Preview PDF
Crossref (1)