Performance Estimation of Heat Exchanger Operates By Evaporative Cooling Manner
...Show More Authors

        In this study the design and installation of evaporative air cooler was carried out using completely outdoor air (fresh air) according to two stage evaporative cooling principle. The laboratory equipment was installed by designing and manufacturing a cross flow plate heat exchanger, where aluminum plates used for this purpose with dimensions (50 × 30 × 40 cm). The surfaces of heat exchanger were covered by sawdust from wetted channels side, to increase the percentage of wetting these surfaces and hence improve the performance and efficiency of air cooler.

        An experimental study was carried out to estimate the performance of cooling system, where some of the dominant effective parameters were studied like air flow rate and flow rate and effect the static pressure drop of air and the heat transfer of performance .Air flow rate was ranged between (142.90 to 1461.50 m3 / hr) and water flow rate was varied from (144 L / hr) to (1050 L / hr).

        The experimental results showed that the optimum flow rate of air prepared by the air cooler is (824.7 m3 / hr), As it to be seen from the study that treating the heat exchanger surfaces by sawdust improves the air cooler efficiency about (10 %), but in the other hand leads to increase the static pressure drop in proportion (21%) approximately, and hence increase consumed power about (9 %).The results also show the air cooler can not be used in regions that have moisture content accedes (11.90 g moisture/kg dry air).

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Wed Mar 20 2019
Journal Name
Al-khwarizmi Engineering Journal
Enhancement of Heat Exchanger Performance by Using Dimpled Tube
...Show More Authors

The enhancement of heat exchanger performance was investigated using dimpled tubes tested at different Reynolds numbers, in the present work four types of dimpled tubes with a specified configuration manufactured, tested and then compared performance with the smooth tube and other passive techniques performance. Two dimpled arrangements along the tube were investigated, these are inline and staggered at constant pitch ratio X/d=4, the test results showed that Nusselts number (heat transfer) of the staggered array is higher than the inline array by 13%.  The effect of different depths of the dimple (14.5 mm and 18.5 mm) has been also investigated; a tube with large dimple diameter enhanced the Nusselts number by about 25% for the ran

... Show More
View Publication Preview PDF
Crossref (2)
Crossref
Publication Date
Sat Sep 01 2007
Journal Name
Al-khwarizmi Engineering Journal
Parametric study of thermal behavior of thrust chamber cooling channels
...Show More Authors

A numerical investigation is adopted for two dimensional thermal analysis of rocket thrust chamber wall (RL10), employing finite difference model with iterative scheme (implemented under relaxation factor of 0.9 for convergence) to compute temperature distribution within thrust chamber  wall (which is composed of Nickel and Copper layers). The analysis is conducted for different boundary conditions: only convection boundary conditions then combined radiation, convection boundary conditions also for  different aspect ratio (AR) of cooling channel. The results show that Utilizing cooling channels of high aspect ratio leads to decrease in temperature variation across thrust chamber wall, while no effects on heat transferred to the

... Show More
View Publication Preview PDF
Publication Date
Sun Dec 17 2017
Journal Name
Al-khwarizmi Engineering Journal
Experimental Study Using the Passive Solar Chimney for Evaporative Cooling With PCM and CFM as a Thermal Energy Storage
...Show More Authors

 

      In this work, a test room was built in Baghdad city, with (2*1.5*1.5) m3  in dimensions, while the solar chimneys (SC) were designed with aspect ratio (ar) bigger than 12. Test room was supplied by many solar collectors; vertical single side of air pass with ar equals 25, and tilted 45o double side of air passes with ar equals 50 for each pass, both collectors consist of flat thermal energy storage box collector (TESB) that covered by transparent clear acrylic sheet, third type of collector is array of evacuated tubular collectors with thermosyphon in 45o instelled  in the bottom of TESB of vertical SC. The TESB was

... Show More
View Publication Preview PDF
Publication Date
Tue Aug 01 2023
Journal Name
Baghdad Science Journal
Performance Evaluation of a Triple Concentric Tube Heat Exchanger Using Deionized Water and Oil-40
...Show More Authors

This study examines experimentally the performance of a horizontal triple concentric tube heat exchanger TCTHE made of copper metal using water as cooling fluid and oil-40 as hot fluid. Hot fluid enters the inner annular tube of the TCTHE in a direction at a temperature of 50, 60 and 70 oC and a flow rate of 20 l/hr. On the other hand, the cooling fluid enters the inner tube and the outer annular tube in the reverse direction (counter current flow) at a temperature of 25 oC and flow rates of 10, 15, 20, 25, 30 and 35 l/hr. The TCTHE is composed of three copper tubes with outer diameters of 34.925 mm, 22.25 mm, and 9.525 mm, and thicknesses of 1.27 mm, 1.143 mm, and 0.762 mm, respectively. TCTHE tube's length was 670

... Show More
View Publication Preview PDF
Scopus Crossref
Publication Date
Fri Jan 01 2016
Journal Name
Journal Of Engineering
Thermal Characteristics of Closed Wet Cooling Tower Using Different Heat Exchanger Tubes Arrangement
...Show More Authors

This paper presents thermal characteristics analysis of a modified Closed Wet Cooling Tower (CWCT) based on heat and mass transfer principles to improve the performance of this tower in Iraq. A prototype of CWCT optimized by added packing was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of the air measured at intermediate points of the heat exchanger and packing. Heat exchangers consist of four rows and eight columns for an inline tubes arrangement and six rows and five columns f

... Show More
View Publication Preview PDF
Publication Date
Sun Jan 01 2017
Journal Name
Journal Of Engineering
Performance Enhancement of an Air Cooled Air Conditioner with Evaporative Water Mist Pre-cooling
...Show More Authors

The present paper deals with experimental investigation of the performance of air cooled split air conditioner, with evaporative water mist pre cooling to increase the cooling capacity and reduce the consumption power under hot and dry climate. This investigation considers how the performance can be enhanced by using water mist to pre-cool ambient air entering the condensers by adiabatic cooling process which depends on the ambient air wet bulb temperature; as well the condensing temperature and condensing pressure will be decreased accordingly. So the cooling capacity would be increased and consumption power would be decreased, consequently the energy ratio, EER would be improved. The performance of air cooled air conditioner with water

... Show More
View Publication Preview PDF
Publication Date
Tue Dec 30 2014
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Performance Evaluation of Three Phase Spray Direct Contact Heat Exchanger
...Show More Authors

 

The present investigation deals with experimental study of three-phase direct-contact heat exchanger, for water-Freon R11 system, where water is the continuous phase (liquid) and Freon R11 (liquid-gas) is the dispersed phase. The test section consisted of a cylindrical Perspex column with inner diameter 8cm and 1.2m long, in which, water was to be confined. Liquid Freon R11 drops were injected into the hot water filled column, through a special design of distributors at the bottom of the column. The liquid Freon R11 drops rose on their way up and evaporated into two-phase bubbles at atmospheric pressure. The study was devoted to express the effect of process variables such as c

... Show More
View Publication Preview PDF
Publication Date
Mon Mar 29 2021
Journal Name
Journal Of Engineering
Experimental Investigation of Thermal Performance of Aluminum Foil Coated with Polyester in a Direct Evaporative Cooling System
...Show More Authors

An experimental study was carried out for an evaporative cooling system in order to investigate the effect of using an aluminum pad coated with fabric polyester. In the present work, it was considered to use a new different type of cooling medium and test its performance during the change in the wet-bulb temperature and dry-bulb temperature of the supply air outside of the pad, the relative humidity of the supply air, the amount of air supplied (300-600) CFM and also the change of the amount of circulated water (1.75, 2.5, 4.5) liter per minute. A decrease in the WBT of the air was obtained, whereas the WBT of the air entering the pad was 26.5 . In contrast, the WBT of the outside air had reached 23  even though eva

... Show More
View Publication Preview PDF
Crossref
Publication Date
Thu Feb 01 2024
Journal Name
Journal Of Engineering
Performance Evaluation of Two Stages Parallel Flow Indirect Evaporative Cooling with Aspen Pads in Baghdad Climate Conditions
...Show More Authors

This study delves into the realm of advanced cooling techniques by examining the performance of a two-stage parallel flow indirect evaporative cooling system enhanced with aspen pads in the challenging climate of Baghdad. The objective was to achieve average air dry bulb temperatures (43 oC) below the ambient wet bulb temperatures (24.95 oC) with an average relative humidity of 23%, aiming for unparalleled cooling efficiency. The research experiment was carried out in the urban environment of Baghdad, characterized by high temperature conditions. The investigation focused on the potential of the two-stage parallel flow setup, combined with the cooling capability of aspen pads, to surpass the limitat

... Show More
View Publication Preview PDF
Crossref
Publication Date
Mon Apr 01 2019
Journal Name
Journal Of Engineering
Two Stage Evaporative Cooling of Residential Building Using Geothermal Energy
...Show More Authors

The weather of Iraq has longer summer season compared with other countries. The ambient temperature during this season reaches over 50 OC which makes the evaporative cooling system suitable for this climate. In present work, the two-stage evaporative cooling system is studied. The first stage is indirect evaporative cooling (IEC) represented by two heat exchangers with the groundwater flow rate (5 L/min). The second stage is direct evaporative cooling (DEC) which represents three pads with groundwater flow rates of (4.5 L/min). The experimental work was conducted in July, August, September, and October in Baghdad. Results showed that overall evaporative efficiency of the system (two coils with three pads each

... Show More
View Publication Preview PDF
Crossref (4)
Crossref