Performance Estimation of Heat Exchanger Operates By Evaporative Cooling Manner
...Show More Authors

        In this study the design and installation of evaporative air cooler was carried out using completely outdoor air (fresh air) according to two stage evaporative cooling principle. The laboratory equipment was installed by designing and manufacturing a cross flow plate heat exchanger, where aluminum plates used for this purpose with dimensions (50 × 30 × 40 cm). The surfaces of heat exchanger were covered by sawdust from wetted channels side, to increase the percentage of wetting these surfaces and hence improve the performance and efficiency of air cooler.

        An experimental study was carried out to estimate the performance of cooling system, where some of the dominant effective parameters were studied like air flow rate and flow rate and effect the static pressure drop of air and the heat transfer of performance .Air flow rate was ranged between (142.90 to 1461.50 m3 / hr) and water flow rate was varied from (144 L / hr) to (1050 L / hr).

        The experimental results showed that the optimum flow rate of air prepared by the air cooler is (824.7 m3 / hr), As it to be seen from the study that treating the heat exchanger surfaces by sawdust improves the air cooler efficiency about (10 %), but in the other hand leads to increase the static pressure drop in proportion (21%) approximately, and hence increase consumed power about (9 %).The results also show the air cooler can not be used in regions that have moisture content accedes (11.90 g moisture/kg dry air).

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Sat Dec 31 2011
Journal Name
Al-khwarizmi Engineering Journal
Effect of Mixed Corrosion Inhibitors in Cooling Water System
...Show More Authors

The effect of mixed corrosion inhibitors in cooling system was evaluated by using carbon steel specimens and weight loss analysis. The carbon steel specimens immersed in mixture of sodium phosphate (Na2 HPO4) used as corrosion inhibitor and sodium glocunate (C6 H11 NaO7) as a scale dispersant at different concentrations (20,40, 60, 80 ppm) and at different temperature (25,50,75 and 100)ºC for (1-5) days. The corrosion inhibitors efficiency was calculated by using uninhibited and inhibited water to give 98.1%. The result of these investigations indicate that the corrosion rate decreases with the increase the corrosion inhibitors concentration at 80 ppm and at 100ºC for 5 days, (i.e,

... Show More
View Publication Preview PDF
Publication Date
Thu May 31 2012
Journal Name
Al-khwarizmi Engineering Journal
An Experimental Study on the Effect of Shape and Location of Vortex Generators Ahead of a Heat Exchanger
...Show More Authors

An experimental study is carried out on the effect of vortex generators (Circular and square) on the flow and heat transfer at variable locations at (X = 0.5, 1.5, 2.5 cm) ahead of a heat exchanger with Reynolds number ranging from 62000< Re < 125000 and heat flux from 3000 ≤ q ≤ 8000 W/m2 .

In the experimental investigation, an apparatus is set up to measure the velocity and temperatures around the heat exchanger.                     

The results show that there is an effect for using vortex generators on heat transfer. Also, heat transfer depends on the shape and location. The circular is found t

... Show More
View Publication Preview PDF
Publication Date
Sat Aug 01 2020
Journal Name
Journal Of Engineering
Experimental Evaluation of Evaporative Cooling for Enhancing Photovoltaic Panels Efficiency Using Underground Water
...Show More Authors

This paper presents an experimental study of cooling photovoltaic (PV) panels using evaporative cooling. Underground (geothermal energy) water used to extract heat from it during cooling and cleaning of PV panels. An experimental test rig was constructed and tested under hot and dusty climate conditions in Baghdad. An active cooling system was used with auxiliary an underground water tank to provide cold water as a coolant over both PV surfaces to reduce its temperature. The cellulose pad has been arranged on the back surface and sprays cooling on the front side. Two identical PV panels modules used: without cooling and evaporative water cooling. The experiments are comprised of four cases: Case (I): backside cooling, Ca

... Show More
View Publication Preview PDF
Crossref (11)
Crossref
Publication Date
Mon May 01 2023
Journal Name
Journal Of Engineering
Experimental Evaluation of PV Panel Efficiency Using Evaporative Cooling Integrated with Water Spraying
...Show More Authors

In this work, an inventive photovoltaic evaporative cooling (PV/EC) hybrid system was constructed and experimentally investigated. The PV/EC hybrid system has the prosperous advantage of producing electrical energy and cooling the PV panel besides providing cooled-humid air. Two cooling techniques were utilized: backside evaporative cooling (case #1) and combined backside evaporative cooling with a front-side water spray technique (case #2). The water spraying on the front side of the PV panel is intermittent to minimize water and power consumption depending on the PV panel temperature. In addition, two pad thicknesses of 5 cm and 10 cm were investigated at three different water flow rates of 1, 2, and 3 lpm. In Case #1,

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Wed Jul 31 2019
Journal Name
Journal Of Engineering
Enhancing Heat Transfer in Tube Heat Exchanger by Inserting Discrete Twisting Tapes with Different Positions
...Show More Authors

Enhancement of heat transfer in the tube heat exchanger is studied experimentally by using discrete twisted tapes. Three different positions were selected for inserting turbulators along tube section (horizontal position by α= 00, inclined position by α= 45 0 and vertical position by α= 900). The space between turbulators was fixed by distributing 5 pieces of these turbulators with pitch ratio    PR = (0.44). Also, the factor of constant heat flux was applied as a boundary condition around the tube test section for all experiments of this investigation, while the flow rates were selected as a variable factor (Reynolds number values vary from 5000 to 15000). The results s

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Mon Dec 31 2012
Journal Name
Al-khwarizmi Engineering Journal
Experimental Study on the Impact of External Geometrical Shape on Free and Forced Convection Time Dependent Average Heat Transfer Coefficient during Cooling Process
...Show More Authors

In this research, an experimental study was conducted to high light the impact of the exterior shape of a cylindrical body on the forced and free convection heat transfer coefficients when the body is hold in the entrance of an air duct. The impact of changing the body location within the air duct and the air speed are also demonstrated. The cylinders were manufactured with circular, triangular and square sections of copper for its high thermal conductivity with appropriate dimensions, while maintaining the surface area of all shapes to be the same. Each cylinder was heated to a certain temperature and put inside the duct at certain locations. The temperature of the cylinder was then monitored. The heat transfer coefficient were then cal

... Show More
View Publication Preview PDF
Publication Date
Sun Dec 30 2007
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Prevention of Scale Formation in Heat Exchanger Pipes by Using Magnetic Field
...Show More Authors

The possibility of using the magnetic field technique in prevention of forming scales in heat exchangers pipes using
hard water in heat transfer processes, also the studying the effective and controllable parameters on the mechanism of
scale formation.
The new designed heat exchanger experimental system was used after carrying out the basic process designs of the
system. This system was used to study the effect of the temperature (40-90 °C) and water flow rate (0.6-1.2 L/min) on
the total hardness with time as a function of precipitation of hardness salts from water and scale formation.
Different magnetic field designs in the heat exchanger experimental system were used to study the effect of magnetic
field design a

... Show More
View Publication Preview PDF
Publication Date
Mon Aug 01 2022
Journal Name
Journal Of Engineering
Mechanical Integrity of Printed Circuit Heat Exchanger
...Show More Authors

The printed circuit heat exchanger is a plate type heat exchanger with a high performance and compact size. Heat exchangers such as this need a unique form of bonding and other techniques to be used in their construction. In this study, the process of joining plates, diffusion bonding, was performed and studied. A special furnace was manufactured for bonding purposes. The bonding process of copper metal was carried out under specific conditions of a high temperature up to 700 oC, high pressure of 3.45 MPa, and in an inert environment (Argon gas) to make tensile samples. The tensile samples are cylindrical shapes containing groves representing the flow channels in the printed circuit heat exchanger and checking their tensile st

... Show More
View Publication Preview PDF
Crossref
Publication Date
Mon Jul 09 2018
Journal Name
Iraqi Journal Of Market Research And Consumer Protection
ESTIMATION OF WATER POLLUTION AND CULTIVATED PLANTS ON THE DIYALA RIVER WITH HEAVY ELEMENTS DURING THE SUMMER BY FLAME ATOMIC ABSORPTION: ESTIMATION OF WATER POLLUTION AND CULTIVATED PLANTS ON THE DIYALA RIVER WITH HEAVY ELEMENTS DURING THE SUMMER BY FLAME ATOMIC ABSORPTION
...Show More Authors

This study was carried out to measure the percentage of heavy metals pollution in the water of the Diyala river and to measure the percentage of contamination of these elements in the leafy vegetables grown on both sides of the Diyala river, which are irrigated by the contaminated river water (celery, radish, lepidium, green onions, beta vulgaris subsp, and malva). Laboratory analysis was achieved to measure the ratio of heavy element contamination (Pb, Fe, Ni, Cd, Zn and Cr) using flame atomic absorption spectrophotometer during the summer months of July and August for the year 2017. The study showed that the elements of zinc, chromium, nickel and cadmium were high concentrations and exceeded. The maximum concentration of these

... Show More
View Publication Preview PDF
Publication Date
Fri Apr 01 2016
Journal Name
Journal Of Engineering
Numerical Study of Heat Transfer Enhancement in Heat Exchanger Using AL2O3 Nanofluids
...Show More Authors

In this study, the flow and heat transfer characteristics of Al2O3-water nanofluids for a range of the Reynolds number of 3000, 4500, 6000 and 7500 with a range of volume concentration of 1%, 2%, 3% and 4% are studied numerically. The test rig consists of cold liquid loop, hot liquid loop and the test section which is counter flow double pipe heat exchanger with 1m length. The inner tube is made of smooth copper with diameter of 15mm. The outer tube is made of smooth copper with diameter of 50mm. The hot liquid flows through the outer tube and the cold liquid (or nanofluid) flow through the inner tube. The boundary condition of this study is thermally insulated the outer wall with uniform velocity a

... Show More
View Publication Preview PDF