Preferred Language
Articles
/
joe-1985
Performance Evaluation of Two Stages Parallel Flow Indirect Evaporative Cooling with Aspen Pads in Baghdad Climate Conditions
...Show More Authors

This study delves into the realm of advanced cooling techniques by examining the performance of a two-stage parallel flow indirect evaporative cooling system enhanced with aspen pads in the challenging climate of Baghdad. The objective was to achieve average air dry bulb temperatures (43 oC) below the ambient wet bulb temperatures (24.95 oC) with an average relative humidity of 23%, aiming for unparalleled cooling efficiency. The research experiment was carried out in the urban environment of Baghdad, characterized by high temperature conditions. The investigation focused on the potential of the two-stage parallel flow setup, combined with the cooling capability of aspen pads, to surpass the limitations imposed by conventional cooling methods. The empirical findings underscored the capacity of the two-stage parallel flow configuration to achieve air-dry bulb temperatures surpassing the ambient wet bulb temperature.

Nonetheless, it was evident that an excessive application of water (exceeding 9 lpm) onto the aspen pads within the wet channels yielded adverse repercussions on the cooler's performance metrics, specifically in terms of wet bulb effectiveness and coefficient of performance. A range of air flows spanning from 150 CMH to 350 CMH was analyzed, revealing the influence of heightened air flow rates on the resultant dry bulb temperatures delivered by the cooling system. Notably, the peak wet-bulb effectiveness registered at 1.08, concurrently yielding a coefficient of performance measuring 7.8.

Crossref
View Publication Preview PDF
Quick Preview PDF
Publication Date
Mon Apr 01 2019
Journal Name
Journal Of Engineering
Two Stage Evaporative Cooling of Residential Building Using Geothermal Energy
...Show More Authors

The weather of Iraq has longer summer season compared with other countries. The ambient temperature during this season reaches over 50 OC which makes the evaporative cooling system suitable for this climate. In present work, the two-stage evaporative cooling system is studied. The first stage is indirect evaporative cooling (IEC) represented by two heat exchangers with the groundwater flow rate (5 L/min). The second stage is direct evaporative cooling (DEC) which represents three pads with groundwater flow rates of (4.5 L/min). The experimental work was conducted in July, August, September, and October in Baghdad. Results showed that overall evaporative efficiency of the system (two coils with three pads each

... Show More
View Publication Preview PDF
Crossref (4)
Crossref
Publication Date
Mon May 01 2023
Journal Name
Journal Of Engineering
Experimental Evaluation of PV Panel Efficiency Using Evaporative Cooling Integrated with Water Spraying
...Show More Authors

In this work, an inventive photovoltaic evaporative cooling (PV/EC) hybrid system was constructed and experimentally investigated. The PV/EC hybrid system has the prosperous advantage of producing electrical energy and cooling the PV panel besides providing cooled-humid air. Two cooling techniques were utilized: backside evaporative cooling (case #1) and combined backside evaporative cooling with a front-side water spray technique (case #2). The water spraying on the front side of the PV panel is intermittent to minimize water and power consumption depending on the PV panel temperature. In addition, two pad thicknesses of 5 cm and 10 cm were investigated at three different water flow rates of 1, 2, and 3 lpm. In Case #1,

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Sun Jan 01 2017
Journal Name
Journal Of Engineering
Performance Enhancement of an Air Cooled Air Conditioner with Evaporative Water Mist Pre-cooling
...Show More Authors

The present paper deals with experimental investigation of the performance of air cooled split air conditioner, with evaporative water mist pre cooling to increase the cooling capacity and reduce the consumption power under hot and dry climate. This investigation considers how the performance can be enhanced by using water mist to pre-cool ambient air entering the condensers by adiabatic cooling process which depends on the ambient air wet bulb temperature; as well the condensing temperature and condensing pressure will be decreased accordingly. So the cooling capacity would be increased and consumption power would be decreased, consequently the energy ratio, EER would be improved. The performance of air cooled air conditioner with water

... Show More
View Publication Preview PDF
Publication Date
Fri Mar 01 2019
Journal Name
Al-khwarizmi Engineering Journal
Performance Estimation of Heat Exchanger Operates By Evaporative Cooling Manner
...Show More Authors

        In this study the design and installation of evaporative air cooler was carried out using completely outdoor air (fresh air) according to two stage evaporative cooling principle. The laboratory equipment was installed by designing and manufacturing a cross flow plate heat exchanger, where aluminum plates used for this purpose with dimensions (50 × 30 × 40 cm). The surfaces of heat exchanger were covered by sawdust from wetted channels side, to increase the percentage of wetting these surfaces and hence improve the performance and efficiency of air cooler.

        An experimental study was carried out to estimate the performance of cooling system, where som

... Show More
View Publication Preview PDF
Publication Date
Mon Mar 29 2021
Journal Name
Journal Of Engineering
Experimental Investigation of Thermal Performance of Aluminum Foil Coated with Polyester in a Direct Evaporative Cooling System
...Show More Authors

An experimental study was carried out for an evaporative cooling system in order to investigate the effect of using an aluminum pad coated with fabric polyester. In the present work, it was considered to use a new different type of cooling medium and test its performance during the change in the wet-bulb temperature and dry-bulb temperature of the supply air outside of the pad, the relative humidity of the supply air, the amount of air supplied (300-600) CFM and also the change of the amount of circulated water (1.75, 2.5, 4.5) liter per minute. A decrease in the WBT of the air was obtained, whereas the WBT of the air entering the pad was 26.5 . In contrast, the WBT of the outside air had reached 23  even though eva

... Show More
View Publication Preview PDF
Crossref
Publication Date
Sat Aug 01 2020
Journal Name
Journal Of Engineering
Experimental Evaluation of Evaporative Cooling for Enhancing Photovoltaic Panels Efficiency Using Underground Water
...Show More Authors

This paper presents an experimental study of cooling photovoltaic (PV) panels using evaporative cooling. Underground (geothermal energy) water used to extract heat from it during cooling and cleaning of PV panels. An experimental test rig was constructed and tested under hot and dusty climate conditions in Baghdad. An active cooling system was used with auxiliary an underground water tank to provide cold water as a coolant over both PV surfaces to reduce its temperature. The cellulose pad has been arranged on the back surface and sprays cooling on the front side. Two identical PV panels modules used: without cooling and evaporative water cooling. The experiments are comprised of four cases: Case (I): backside cooling, Ca

... Show More
View Publication Preview PDF
Crossref (11)
Crossref
Publication Date
Sun Mar 30 2003
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Performance of Countercurrent Flow Cooling Towers
...Show More Authors

View Publication Preview PDF
Publication Date
Sun Jun 30 2013
Journal Name
Al-khwarizmi Engineering Journal
Efficiency Prediction and Performance Characterization of Photovoltaic Solar Panel at Baghdad Climate Conditions
...Show More Authors

The performance of a solar cell under sun radiation is necessary to describe the electrical parameters of the cell. The Prova 200 solar panel analyzer is used for the professional testing of four solar cells at Baghdad climate conditions. Voltage -current characteristics of different area solar cells operated under solar irradiation for testing their quality and determining the optimal operational parameters for maximum electrical output were obtained. A correlation is developed between solar cell efficiency h and the corresponding solar cell parameters; solar irradiance G, maximum power Pmax, and production date P. The average absolute error of the proposed correlation is 5.5% for 40 data points. The results also show th

... Show More
View Publication Preview PDF
Publication Date
Mon Nov 09 2020
Journal Name
Heat Transfer
Experimental performance of cooling photovoltaic panels using geothermal energy in an arid climate
...Show More Authors

View Publication
Scopus (3)
Crossref (3)
Scopus Clarivate Crossref
Publication Date
Tue Mar 31 2015
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Performance of Corrosion Inhibitors Blend for Simulated Industrial Cooling Waters under Dynamic Conditions
...Show More Authors

   The inhibitive action of a blend of sodium nitrite/sodium hexametaphosphate (SN+SHMP) on corrosion of carbon steel in simulated cooling water systems (CWS) has been investigated by weight loss and electrochemical polarization technique. The effect of temperature, velocity, and salts concentrations on corrosion of carbon steel were studied in the absence and presence of mixed inhibiting blend. Also the effect of inhibitors blend concentrations (SN+SHMP), temperatures, and rotational velocity, i.e., Reynolds number (Re) on corrosion rate of carbon steel were investigated using Second-order Rotatable Design (Box-Wilson Design) in performing weight loss and corrosion potential approach. Electrochemical polarization measurements

... Show More
View Publication Preview PDF