Prediction of Raw Water Turbidity at the Intakes of the Water Treatment Plants along Tigris River in Baghdad, Iraq using Frequency Analysis
...Show More Authors

Different frequency distributions models were fitted to the monthly data of raw water Turbidity at water treatment plants (WTPs) along Tigris River in Baghdad. Eight water treatment plants in Baghdad were selected, with raw water turbidity data for the period (2008-2014). The frequency distribution models used in this study are the Normal, Log-normal, Weibull, Exponential and two parameters Gamma type. The Kolmogorov-Smirnov test was used to evaluate the goodness of fit.  The data for years (2008-2011) were used for building the models. The best fitted distributions were Log-Normal (LN) for Al-Karkh, Al-Wathbah, Al-Qadisiya, Al-Dawrah and, Al-Rashid WTPs. Gamma distribution fitted well for East Tigris and Al-Karamah WTPs. As for Al-Wehda WTP Weibull distributions, was the best model. The best fitted distributions were used to forecast ten sets of monthly data for each plant that were compared with the observed data for years (2012-2014). The Kolmogorov-Smirnov test results indicated the capability of these models to produce data that has the same frequency distribution of the observed data. Moreover the frequency of occurrence of the observed and generated series in each plant indicated the capability of the model to produce results with frequency occurrence of probabilities of turbidity values > 50, 80, 100, 120, and 150 NTU.

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Mon May 01 2023
Journal Name
Journal Of Engineering
Design Comparison between the Gravity and Pressure Sand Filters for Water Treatment, Review
...Show More Authors

Hygienic engineering has dedicated a lot of time and energy to studying water filtration because of how important it is to human health. Thorough familiarity with the filtration process is essential for the design engineer to keep up with and profit from advances in filtering technology and equipment as the properties of raw water continue to change. Because it removes sediment, chemicals, odors, and microbes, filtration is an integral part of the water purification process. The most popular technique for treating surface water for municipal water supply is considered fast sand filtration, which can be achieved using either gravity or pressure sand filters. Predicting the performance of units in water treatment plants is

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Thu Dec 29 2016
Journal Name
Ibn Al-haitham Journal For Pure And Applied Sciences
Potability of Well Water in Falluja City ,Iraq.
...Show More Authors

  The Falluja residents had resorted to the underground water as an alternative to the surface waters of the Euphrates river passing near the city, through digging wells inside gardens of Mosques in the city during spring 2005. The present study aims to indicate the quality of these waters and demonstrates the extent of their suitability for drinking . For this purpose, 21 randomly distributed wells were chosen during August 2005. The water characters were measured ; the average values of 21 wells were as follows : Water temp .(22.6C Ù’ â—Œ ) , EC (4,11 msem .\cm ), pH (7.15 ) and concentration of cations : Na (439mg\l) ;K (275mg\l) ; Li (0,28mg\l), Ba (15.2 mg\l) and (133mg\l). These character is ties were compared with the

... Show More
View Publication Preview PDF
Publication Date
Thu Oct 01 2020
Journal Name
Journal Of Engineering
Electrocoagulation for Treatment of Simulated Blowdown Water Of Cooling Tower
...Show More Authors

This study investigates the results of electrocoagulation (EC) using aluminum (Al) electrodes as anode and stainless steel (grade 316) as a cathode for removing silica, calcium, and magnesium ions from simulated cooling tower blowdown waters. The simulated water contains (50 mg/l silica, 508 mg/l calcium, and 292 mg/l magnesium). The influence of different experimental parameters, such as current density (0.5, 1, and 2 mA/cm2), initial pH(5,7, and 10), the temperature of the simulated solution(250C and 35 0C), and electrolysis time was studied. The highest removal efficiency of 80.183%, 99.21%, and 98.06% for calcium, silica, and magnesium ions, respectively, were obtained at a current de

... Show More
View Publication Preview PDF
Crossref (5)
Crossref
Publication Date
Fri Jan 01 2021
Journal Name
Aip Conference Proceedings
Radon concentrations assessment in tap water for different areas in Baghdad city using Rad7
...Show More Authors

View Publication
Scopus (1)
Scopus Crossref
Publication Date
Sun Apr 09 2017
Journal Name
Ibn Al-haitham Journal For Pure And Applied Sciences
Study of the Density of Crustacean Zooplankton and Some Environmental Factors Inside and Outside the Cages Breeding Fish in the Tigris River (Al Rashidiya area) Baghdad
...Show More Authors

Two orders of zooblankton,were studied Cladocera and Copepeda in two classes Calanoida and Cyclopoda, where it was studied inside floating cages and for breeding fish placed in the Tigris River in the Rashidiya area. Has been study The population density of zooplankton groups and measure some chemical and physical characters, was studie where she collected samples of zooplankton and water from two locations of cages (inside the cages, after 100m from cages). The study was conducted within six months from January to the end of June 2014 during which there was study of the Wallace pH, water temperature, biological oxygen demand and dissolved oxygen, as to the zooplankton study the species disappeared inside cages of fish and existed after

... Show More
View Publication Preview PDF
Publication Date
Mon May 08 2017
Journal Name
Ibn Al-haitham Journal For Pure And Applied Sciences
Test of the Treatment Unit Efficiency, In Soap and Detergents Factory , In Improving The Quality Of Industrial Waste Water.
...Show More Authors

This study which was carried out from Jan /2010 to Jan/2011,evolution of the efficiency
of treatment unit of al-Ameen factory , a subsidiary of Vegetable Oils General Company in
al- Za
,
faraniya /Sa
,
idea district /South of Baghdad ,via examing the waters coming out of
treatment unit and the role of this unit in improving waters quality , especially in physical and
chemical characteristics to be main factors in studying water's quality, such as temperature
C°,pH,Ec,DO,BOD5,NO3,TDS,PO4
-3
.
The results showed that the characteristics of treated treated water excepte of the Ec
factor were within the acceptable limits,in spite of the high concentration entering the unit .
This confirms t

... Show More
View Publication Preview PDF
Publication Date
Tue Jun 01 2021
Journal Name
Iop Conference Series: Earth And Environmental Science
Performance Evaluation of Al-Karkh Water Treatment Plant Using Model-driven and Data-Driven Models
...Show More Authors
Abstract<p>There is a great operational risk to control the day-to-day management in water treatment plants, so water companies are looking for solutions to predict how the treatment processes may be improved due to the increased pressure to remain competitive. This study focused on the mathematical modeling of water treatment processes with the primary motivation to provide tools that can be used to predict the performance of the treatment to enable better control of uncertainty and risk. This research included choosing the most important variables affecting quality standards using the correlation test. According to this test, it was found that the important parameters of raw water: Total Hardn</p> ... Show More
View Publication
Scopus (1)
Crossref (2)
Scopus Crossref
Publication Date
Mon May 01 2023
Journal Name
Journal Of Engineering
Design Comparison between the Gravity and Pressure Sand Filters for Water Treatment, Review
...Show More Authors

Hygienic engineering has dedicated a lot of time and energy to studying water filtration because of how important it is to human health. Thorough familiarity with the filtration process is essential for the design engineer to keep up with and profit from advances in filtering technology and equipment as the properties of raw water continue to change. Because it removes sediment, chemicals, odors, and microbes, filtration is an integral part of the water purification process. The most popular technique for treating surface water for municipal water supply is considered fast sand filtration, which can be achieved using either gravity or pressure sand filters. Predicting the performance of units in water treatment plants is a basic pri

... Show More
View Publication
Crossref (1)
Crossref
Publication Date
Sat Jan 01 2022
Journal Name
Journal Of The Mechanical Behavior Of Materials.
Calibration and analysis of the potable water network in the Al-Yarmouk region employing WaterGEMS and GIS
...Show More Authors
Abstract<p>Water supply and distribution networks play an important role in our daily activities. They make a substantial contribution to public health by providing potable water for public consumption and non-potable applications such as firefighters and other purposes such as irrigation. This study used ArcMap 10.8 and WaterGEMS CONNECT Edition update 1 version to create a hydraulic network model to simulate the pipes’ network. Detailed network information, including pipe lengths, layouts, and diameters, was given by the Baghdad Water Department. The TUF-2000H Handheld digital ultrasonic flow meter has been used to measure the water flows in the network’s source nodes. In eight junctions, </p> ... Show More
Scopus (5)
Crossref (4)
Scopus Clarivate Crossref
Publication Date
Mon Aug 01 2011
Journal Name
Journal Of Engineering
Preservation of Required Chlorine Concentration in Baghdad Water Supply Networks using On-Site Chlorine Injection
...Show More Authors

The chlorine concentration variation in Baghdad water networks was studied. The
chlorine data were collected from Mayoralty of Baghdad and Ministry of Environment
(MOE) for the networks for both sides of the city Karkh and Rasafa for (2008-2009). The
study of these data indicates that there are no systematic testing program .Classified GIS
maps showed that the areas far from the treatment plants have almost always low
chlorine concentration .This indicates that the problem of the low chlorine concentration
in the far areas is due to cracks of pipe along the conveyance path ,as expected. The area's
most frequently have low concentration are Al-sadir,Al-Kadhimya, and Al-Amiria . It
was found also that the chlorine c

... Show More
View Publication Preview PDF
Crossref