The evacuated tube solar collector ETC is studied intensively and extensively by experimental and
theoretical works, in order to investigate its performance and enhancement of heat transfer, for Baghdad climate
from April 2011 till the end of March 2012. Experimental work is carried out on a well instrumented collector
consists of 16 evacuated tubes of aspect ratio 38.6 and thermally insulated tank of volume 112L. The relation
between convective heat transfer and natural circulation inside the tube is estimated, collector efficiency, effect of
tube tilt angles, incidence angle modifier, The solar heating system is investigated under different loads pattern (i.e
closed and open flow) to evaluate the heat loss coefficient from tank and tubes, test the collector with various
aspect ratios (32.9 and 27.2). The enhancement in collector performance is studied by using two reflectors (Flat
Plate and Curved Plate) and nanofluid (Water-AL2O3).Theoretical work is run by software (Fluent 6.3), to compute
the velocity and temperature profiles within the tube, for different tube diameters, effect of tube junction angle and
stagnant region in the bottom of the evacuated tube. The experimental results shows that the heat loss coefficient
for tube is W/m2.K and for tank is W/m2.K, the maximum collector temperature is 79°C in winter and
99°C in summer, while that belong to nanofluid collector is 99°C in winter. The best tilted angle (optimum) of
evacuated tube is 41° annually. The collector efficiency increased when using nanofluid of (1, 0.6, 0.3)% volume
fraction as(28.4, 6.8, 0.6)% respectively. The efficiency decreases as (33, 62)% when decreasing tube aspect ratio
from 38.6% to 32.9% and 27.2% respectively. An increase of (16.9 and 7.08)% in collector efficiency is obtained
when using curved and flat plate reflectors respectively. From simulation the best junction angle of the tank is
22.5°. The stagnant region is influenced with changing heat flux, tilted angle and aspect ratio.
Abstract: The natural dye, Curcumin, was extracted from Curcuma longa using as a sensitizer in two types of dye sensitized solar cell (DSSC), and their characteristics were studied. The absorption spectrum of the dye solutions, as well as the wavelength of the maximum absorbance of the dye loaded TiO2 film has been studied. The X-Ray diffraction pattern of TiO2 film made with Doctor-Blading technique shown that the grain size of TiO2 was equal to be 40 nm. The electrical performances in terms of short circuit current, open circuit voltage and power conversion efficiency of cells were investigated.
This work is concerned with the design and performance evaluation of a shell and double concentric tubes heat exchanger using Solid Works and ANSY (Computational Fluid Dynamics).
Computational fluid dynamics technique which is a computer-based analysis is used to simulate the heat exchanger involving fluid flow, heat transfer. CFD resolve the entire heat exchanger in discrete elements to find: (1) the temperature gradients, (2) pressure distribution, and (3) velocity vectors. The RNG k-ε model of turbulence is used to determining the accurate results from CFD.
The heat exchanger design for this work consisted of a shell and eight double concentric tubes. The number of inlets are three and that of o
... Show MoreAlthough renewable energy systems have become an interesting global issue, it is not continuous either daily or seasonally. Latent heat energy storage (LHES) is one of the suitable solutions for this problem. LHES becomes a basic element in renewable energy systems. LHES compensate for the energy lack when these systems are at low production conditions. The present work considered a shell and tube LHES for numerical investigation of the tube rotation influence on the melting process. The simulation and calculations were carried out using ANSYS Fluent software. Paraffin wax represents the phase change material (PCM) in this work, while water was selected to be the heat transfer fluid (HTF). The calculations were carried o
... Show MoreThe fouling depositions of crude oil stream were studied theoretically in a shell and tube heat exchanger to investigate the effect of depositions on the heat transfer process. The employed heat exchanger was with steam flowing in the inner tubes and crude oil in the shell at different velocities and bulk temperatures. It is assumed that fouling occurs only on the heated stream side (crude oil). The analysis was carried out for turbulent flow heat transfer conditions with wide range of Reynolds number, bulk temperature and time. Many previously proposed models for fouling resistance were employed to estimate a new model for fouling rate. It is found that the fouling rate and consequently the heat transfer coefficient were affected by Rey
... Show MoreThe effects of T-shaped fins on the improvement of phase change materials (PCM) melting are numerically investigated in vertical triple-tube storage containment. The PCM is held in the middle pipe of a triple-pipe heat exchanger while the heat transfer fluid flows through the internal and external pipes. The dimension effects of the T-shaped fins on the melting process of the PCM are investigated to determine the optimum case. Results indicate that while using T-shaped fins improves the melting performance of the PCM, the improvement potential is mainly governed by the fin’s body rather than the head. Hence, the proposed T-shaped fin did not noticeably improve melting at the bottom of the PCM domain; additionally, a flat fin is ad
... Show MoreThis study concerns a new type of heat exchangers, which is that of shell-and-double concentric tube heat exchangers. The case studies include both design calculations and performance calculations.
The new heat exchanger design was conducted according to Kern method. The volumetric flow rates were 3.6 m3/h and 7.63 m3/h for the hot oil and water respectively. The experimental parameters studied were: temperature, flow rate of hot oil, flow rate of cold water and pressure drop.
A comparison was made for the theoretical and experimental results and it was found that the percentage error for the hot oil outlet temperature was (- 1.6%). The percentage
... Show MoreFlat-plate collector considers most common types of collectors, for ease of manufacturing and low price compared with other collectors. The main aim of the present work is to increase the efficiency of the collector, which can be achieved by improving the heat transfer and minimize heat loss experimentally. Five types of solar air collectors have been tested, which conventional channel with a smooth absorber plate (model I), dual channel with a smooth absorber plate (model II), dual channel with perforating “V” corrugated absorber plate (model III), dual channel with internal attached wire mesh (model Ⅳ), and dual channel with absorber sheet of transparent honeycomb, (model Ⅴ). The dual channel collector used for
... Show More|
In this work, an experimental investigation has been done for heat transfer by natural-convection through a horizontal concentric annulus with porous media effects. The porous structure in gap spacing consists of a glass balls and replaced by plastic (PVC) balls with different sizes. The outer surface of outer tube is isothermally cooled while the outer surface of inner tube is heated with constant heat flux condition. The inner tube is heated with different supplied electrical power levels. Four different radius ratios of annulus are used. The effects of porous media material, particles size and annulus radius ratio on heat dissipation in terms of average Nusselt number have been analyzed. |