Fire Flame Influence on the Behavior of reinforced Concrete Beams Affected by Repeated Load
...Show More Authors

The influence and hazard of fire flame are one of the most important parameters that affecting the durability and strength of structural members. This research studied the influence of fire flame on the behavior of reinforced concrete beams affected by repeated load. Nine self- compacted reinforced concrete beams were castellated, all have the same geometric layout (0.15x0.15x1.00) m, reinforcement details and compressive strength (50 Mpa).

To estimate the effect of fire flame disaster, four temperatures were adopted (200, 300, 400 and 500) oC and two method of cooling were used (graduated and sudden). In the first cooling method, graduated, the tested beams were leaved to cool in air while in the second method, sudden, water splash was used to reduce the temperature. Eight of the tested beams were divided in to four groups, each were burned to one of the adopted temperature for about half an hour and cooled by the adopted cooling methods (one by sudden cooling and the other by graduated cooling). After burning and cooling the beams were tested under the effect of repeated load (loading – unloading) for five cycle and then up to failure.

As a compared with the non- burned beam, the results indicated that the ultimate load capacity of the tested beams were reduced by (16, 23, 54 and 71)% after being burned to (200, 300, 400 and 500) oC , respectively, for a case of sudden cooling and by (8, 14, 36 and 64)% , respectively, for a case of graduated cooling. It was also found that the effect of sudden cooling was greater than that in a case of graduated cooling.

Regarding the failure mode, there was a different between the non-burred beam and the other ones even that all of them had the same geometric layout, compressive strength and reinforcement details. The failure mode for all burned beams was combined shear- flexure failure which was belong to the reduction in the compressive strength of the concrete due to the effect of the temperature rising , while the failure mode of the non-burned beam was flexure failure which was compatible with the preliminary design. It was also detected that the residual deflection proportion directly with the temperature, as the temperature increase to (200, 300, 400 and 500) oC the residual deflection compared with the non-burned beam increased by (32, 48, 326 and 358)% for a case of sudden cooling and by (13, 29, 303 and 332)%  for a case of graduated cooling. Another effect was appear represented by the method of cooling, the results showed that the sudden cooling had more effect on the residual deflection than the graduated cooling by (15-6)% approximately. To vanish the residual deflection, numbers of cycle (loading-unloading) were required. It was found that this number increase as the temperature of burning increased and it’s also larger in a case of sudden cooling.

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Mon Apr 04 2022
Journal Name
Journal Of Educational And Psychological Researches
The Role of Satellite Channels in Imparting Behavior to Children from the Point of View of their Parents in Tulkarm City
...Show More Authors

This study aims to identify the role of satellite channels in imparting behavior to children from the point of view of their parents in Tulkarm city. The researcher used a descriptive technique. A sample of (18000) males and females married couples was used above 20 years old in the city of Tulkarm. The study sample size is (201) married couples. It took place in September 2020. The questionnaire was the main tool for collecting data. The study found that the total degree of satellite channels contribution in imparting negative behaviors to children was high, as it reached (72.20%). The total degree of the role of satellite channels in imparting positive behaviors to children was medium, reaching (69.20%). Moreover, the results also indi

... Show More
View Publication Preview PDF
Publication Date
Tue Oct 01 2019
Journal Name
2019 12th International Conference On Developments In Esystems Engineering (dese)
Structural Rehabilitation on Continuous Post-Tensioned Prestressed Concrete Box-Girder Bridge Exposed to Explosion: A Case Study
...Show More Authors

View Publication
Crossref (1)
Scopus Clarivate Crossref
Publication Date
Fri Jun 29 2018
Journal Name
Journal Of Engineering
Finite Element Modeling and Parametric Study on Floor Steel Beam Concrete Slab System in Non-Composite Action.
...Show More Authors

This study aims to show, the strength of steel beam-concrete slab system without using shear connectors (known as a non-composite action), where the effect of the friction force between the concrete slab and the steel beam has been investigated, by using finite element simulation.

The proposed finite element model has been verified based on comparison with an experimental work. Then, the model was adopted to study the system strength with a different steel beam and concrete slab profile. ABAQUS has been adopted in the preparation of all numerical models for this study.

After validation of the numerical models, a parametric study was conducted, with linear and non-linear Regression analysis. An equation re

... Show More
View Publication Preview PDF
Crossref (2)
Crossref
Publication Date
Fri Mar 01 2024
Journal Name
Construction And Building Materials
Uni- and tri-axial tests and property characterization for thermomechanical effect on hydrated lime modified asphalt concrete
...Show More Authors

Permanent deformation, fatigue and thermal cracking are the three typical distresses of flexible pavement. Using hydrated lime (HL) into the conventional limestone mineral additive has been widely practiced, including in Europe, to improve the mechanical properties of hot mix asphalt (HMA) concrete and as the result the durability of the constructed pavement. Large number of experimental studies have been reported to find the optimum addition of HL for the improvement on HMA concrete mechanical properties, moisture susceptibility and fatigue resistance. Pavement in service is under complex thermomechanical stress-strain conditions due to coupled atmospheric and surrounding environment temperature variation and the traffic loading. To predic

... Show More
View Publication
Scopus (4)
Crossref (3)
Scopus Clarivate Crossref
Publication Date
Sat Feb 01 2020
Journal Name
Structures
Experimental and numerical study on wrapping concrete cylinders post heating and cooling under preload using CFRP fabrics
...Show More Authors

This paper reports test results and describes a numerical investigation of the effectiveness of using carbon fibre reinforced polymer (CFRP) fabrics for strengthening concrete cylinders that have been undamaged and damaged due to heating under preload. The purpose of this research was to investigate whether there is any difference in the performance of CFRP-wrapped cylinders if the wrapping is done under preload, and those for which neither heating, cooling nor wrapping was done under preload. The cylinders were exposed to 30% of maximum load at ambient temperature during heating and cooling before being wrapped under preload. Of 18 Ø 100 × 200 mm identical cylinders, 6 were left as control samples without heating, 12 were exposed t

... Show More
Scopus (15)
Crossref (11)
Scopus Clarivate Crossref
Publication Date
Fri Oct 01 2010
Journal Name
Iraqi Journal Of Physics
Effect of the Thickness and Annealing Temperature on the Structural Properties of Thin CdS Films Prepared by Thermal Evaporation
...Show More Authors

A thin CdS Films have been evaporated by thermal evaporation technique with different thicknesses (500, 1000, 1500 and 2000Å) and different duration times of annealing (60, 120 180 minutes) under 573 K annealing temperature, the vacuum was about 8 × 10-5 mbar and substrate temperature was 423 K. The structural properties of the films have been studied by X- ray diffraction technique (XRD). The crystal growth became stronger and more oriented as the film thickness (T) and duration time of annealing ( Ta) increases.

View Publication Preview PDF
Publication Date
Sun Jun 01 2014
Journal Name
Baghdad Science Journal
The Effect of Annealing on The Structural and Optical Properties of Copper Oxide Thin Films Prepared by SILAR Method
...Show More Authors

Copper oxide thin films were deposited on glass substrate using Successive Ionic Layer Adsorption and Reaction (SILAR) method at room temperature. The thickness of the thin films was around 0.43?m.Copper oxide thin films were annealed in air at (200, 300 and 400°C for 45min.The film structure properties were characterized by x-ray diffraction (XRD). XRD patterns indicated the presence of polycrystalline CuO. The average grain size is calculated from the X-rays pattern, it is found that the grain size increased with increasing annealing temperature. Optical transmitter microscope (OTM) and atomic force microscope (AFM) was also used. Direct band gap values of 2.2 eV for an annealed sample and (2, 1.5, 1.4) eV at 200, 300,400oC respect

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Fri Nov 11 2022
Journal Name
Journal Of Accounting And Financial Studies ( Jafs )
The initiative of the Central Bank of Iraq and its impact on some banking activities provided by specialized banks
...Show More Authors

Specialized banks provide their banking activities to their customers at interest rates that are determined according to the approved bank policy, which is almost similar to most or most banks. To satisfy the financial desires of customers and at the same time it is a source of the bank's profits, However, these banks have been introduced to new services that they provide with the funds of the Central Bank initiative launched at the beginning of (2016) to address the economic stagnation that befell the country due to the (financial security) crisis that the country faced in 2014. To put forward initiatives amounting to nearly (15) trillion dinars, which were put forward through private commercial and Islamic banks and specialized

... Show More
View Publication Preview PDF
Publication Date
Wed Dec 01 2010
Journal Name
Iraqi Journal Of Physics
The effect of anode temperature on the Optical characteristic of Se films prepared by direct current planar magnetron sputtering
...Show More Authors

This work describes, selenium (Se) films were deposited on clean glass substrates by dc planar magnetron sputtering technique.The dependence of sputtering deposition rate of Se film deposited on pressure and DC power has been studied. The optimum argon pressure has range (4x10-1 -8x10-2 )mbar. The optical properties such as absorption coefficient (α) was determined using the absorbance and transmission measurement from UnicoUV-2102 PC spectrophotometer, at normal incidence of light in the wavelength range of 200-850 nm. And also we calculated optical constants(refractive index (n), dielectric constant (εi,r), and Extinction coefficient (κ) for selenium films.

View Publication Preview PDF
Publication Date
Sun Jul 09 2023
Journal Name
Journal Of Engineering
Fabricating a new Rheometer for Concrete
...Show More Authors

A new concrete rheometer is introduced including its innovation, actual design, working rules,
calibration, and reliability. A modified design of Tattersall two-point device is created. Some of
components are purchased from local and foreign markets, while other components and the
manufacturing process are locally fabricated. The matching viscosity method of determining the mixer
viscometer constants is demonstrated and followed to relate torque and rotational speed to yield stress
and viscosity (Bingham parameters). The calibration procedures and its calculation are explained.
Water is used as a Newtonian fluid, while; cement paste (cement + water) with w/c ratio equal to
(0.442) is used as a non-Newtonian fluid. Th

... Show More
View Publication Preview PDF
Crossref