Preferred Language
Articles
/
bsj-526
Performance evolution of a hybrid thermal solar air conditioning system and compare it with a traditional system according to Iraq weather
...Show More Authors

In a hybrid cooling solar thermal systems , a solar collector is used to convert solar energy into heat energy in order to super heat the refrigerant leaving the compressor, and this process helps in the transformation of refrigerant state from gaseous state to the liquid state in upper two-thirds of the condenser instead of the lower two-thirds such as in the traditional air-conditioning systems and this will reduce the energy needed to run the process of cooling .In this research two systems with a capacity of 2 tons each were used, a hybrid air-conditioning system with an evacuated tubes solar collector and a traditional air-conditioning system . The refrigerant of each type was R22.The comparison was in the amount of energy and current consumption of the two systems at the same operating conditions. The energy consumed and the current of the hybrid system were less than the traditional air-conditioning system by 12% and 28.6% respectively, which means that there is a saving in the energy and current consumption as a result of the use of the solar thermal collector.

Crossref
View Publication Preview PDF
Quick Preview PDF
Publication Date
Mon Oct 01 2018
Journal Name
Journal Of Engineering
Experimental Study of Hybrid Solar Air Conditioning System in Iraq
...Show More Authors

In this paper, an experimental study of the thermal performance for hybrid solar air conditioning system was carried out, to investigate system suitability for the hot climate in Iraq. The system consists of vapor compression unit combined with evacuated tube solar collector and liquid storage tank. A three-way valve was installed after the compressor to control the direction flow of the refrigerant, either to the storage tank or directly to the condenser. The performance parameters were collected by data logger to display and record in the computer by using LabVIEW software. The results show that the average coefficient of performance of hybrid solar air conditioning system (R=1) was about 2.42 to 2.77 and the average p

... Show More
View Publication Preview PDF
Crossref (2)
Crossref
Publication Date
Sat Dec 01 2018
Journal Name
Al-khwarizmi Engineering Journal
Enhancement of Hybrid Solar Air Conditioning System using a New Control Strategy
...Show More Authors

Enhancement of the performance for hybrid solar air conditioning system was presented in this paper. The refrigerant temperature leaving the condenser was controlled using three-way valve, this valve was installed after the compressor to regulate refrigerant flow rate towards the solar system. A control system using data logger, sensors and computer was proposed to set the opening valve ratio. The function of control program using LabVIEW software is to obtain a minimum refrigerant temperature from the condenser outlet to enhance the overall COP of the unit by increasing the degree of subcooled refrigerant. A variable load electrical heater with coiled pipe was used instead of the solar collector and the storage tank to simulate the sola

... Show More
View Publication Preview PDF
Crossref
Publication Date
Mon Aug 01 2016
Journal Name
Journal Of Engineering
Modeling and Simulation of Thermal Performance of Solar-Assisted Air Conditioning System under Iraq Climate
...Show More Authors

In Iraq most of the small buildings deployed a conventional air conditioning technology which typically uses electrically driven compressor systems which exhibits several clear disadvantages such as high energy consumption, high electricity at peak loads. In this work a thermal performance of air conditioning system combined with a solar collector is investigated theoretically. The hybrid air conditioner consists of a semi hermetic compressor, water cooled shell and tube condenser, thermal expansion valve and coil with tank evaporator. The theoretical analysis included a simulation for the solar assisted air-conditioning system using EES software to analyze the effect of different parameters on the power consumption of c

... Show More
View Publication Preview PDF
Publication Date
Sun Jun 07 2015
Journal Name
Baghdad Science Journal
The effect of changing the evacuated tube tilt angle and the fluid of the solar collector on the performance of a hybrid solar air conditioning system
...Show More Authors

In the hybrid coolingsolar systems , a solar collectoris used to convertsolar energy intoheat sourcein order to super heat therefrigerant leave thecompressor,andthisprocess helpsin the transformation ofrefrigerant state from gaseous statetothe liquid statein upper two-thirdsof thecondenserinstead of the lower two-thirdssuchas in thetraditional air-conditioning systems and this willreduce theenergyneeded torun the process ofcooling.In this research two hybrid air-conditioning system with an evacuated tube solar collector were used, therefrigerant was R22 and the capacity was 2 tons each.The tilt angle of the evacuated tube solar collector was changed and the solar collector fluid was replaced into oil instead of water.A comparison wasi

... Show More
View Publication Preview PDF
Crossref
Publication Date
Mon Dec 18 2017
Journal Name
Al-khwarizmi Engineering Journal
Using Smart Control System to Enhancement the Split Air Conditioning System Performance
...Show More Authors

In IRAQ, the air conditioners are the principal cause of high electrical demand. In summer, the outer temperature sometimes exceeds 500C which significantly effects on the A/C system performance and power consumed. In the present work, the improvement in mechanical and electrical performance of split A/C system is investigated experimentally and analytically. In this paper, performance and energy saving enhancement of a split-A/C system was experimentally investigated to be efficiently compatible with elevated temperature weathers. This improvement is accomplished via Smart Control System integrate with Proportional-Integral- Differential PID algorithm. The PIC16F877A micro-controller has been programmed with the PID and PWM c

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Sun Feb 24 2019
Journal Name
Iraqi Journal Of Physics
Construction and performance study of a solar - powered hybrid cooling system in Iraq
...Show More Authors

The systems cooling hybrid solar uses solar collector to convert solar energy into the source of heat for roasting Refrigerant outside of the compressor and this process helps in the transformation of Refrigerant from the gas to a liquid state in two-thirds the top of the condenser instead of two-thirds the bottom of the condenser as in Conventional cooling systems and this in turn reduces the energy necessary to lead the process of cooling. The system cooling hybrid use with a capacity of 1 ton and Refrigerant type R22 and the value of current drawn by the system limits (3.9-4.2A), the same value of electric current calculated by the system are  Conventional  within this atmosphere of Iraq, and after taking different readings

... Show More
View Publication Preview PDF
Crossref
Publication Date
Wed Apr 05 2023
Journal Name
Journal Of Engineering
Performance Evaluation of Small Scale Air-Conditioning System Using R22 and Alternative Refrigerants
...Show More Authors

A mathematical model has been formulated to predict the influence of high outdoor air temperature on the performance of small scale air - conditioning system using R22 and alternative refrigerants R290, R407C, R410A. All refrigerants were investigated in the cooling mode operation. The mathematical model results have been validated with experimental data extracted from split type air conditioner of 2 TR capacity. This entailed the construction of an experimental test rig which consists of four main parts. They are, the refrigeration system, psychrometric test facility, measuring instrumentation, and auxiliary systems. The conditioned air was maintained at 25 0C dry bulb and 19 0C wet bulb for all tests. The outdoor ambient air temperatur

... Show More
View Publication Preview PDF
Crossref (3)
Crossref
Publication Date
Fri Mar 01 2019
Journal Name
Al-khwarizmi Engineering Journal
Basement Kind Effects on Air Temperature of a Solar Chimney in Baghdad - Iraq Weather
...Show More Authors

A solar updraft tower power plant (solar tower) is a solar thermal power plant that utilizes a combination of solar

air collector and central updraft tube to generate an induced convective flow which drives pressure staged turbines to generate electricity.

 

 This paper presents practical results of a prototype of a solar chimney with thermal mass, where the glass surface is replaced by transparence plastic cover. The study focused on chimney's basements kind effect on collected air temperatures. Three basements were used: concrete, black concrete and black pebbles basements. The study was conducted in Baghdad from August to November 2009.

The results show that the best chimney efficiency attaine

... Show More
View Publication Preview PDF
Publication Date
Thu Nov 02 2023
Journal Name
Journal Of Engineering
Numerical Simulation of the Thermal Performance of a Tubular Solar Air Heater
...Show More Authors

In this work, a flat-plate solar air heater (FSAH) and a tubular solar air heater (TSAH) were designed and tested numerically. The work investigates the effect of increasing the contact area between the flowing air and the absorber surface of each heater and predicts the expected results before the fabrication of the experimental rig. Three-dimensional two models were designed and simulated by the ANSYS-FLUENT 16 Program. The solar irradiation and ambient air temperature were measured experimentally on December 1st 2022, at the weather conditions of Baghdad City- Iraq, at three air mass flow rates, 0.012 kg/s, 0.032 kg/s, and 0.052 kg/s. The numerical results showed the advantage in the thermal performance of

... Show More
View Publication Preview PDF
Crossref
Publication Date
Mon May 27 2019
Journal Name
Al-khwarizmi Engineering Journal
Effect of Using Air Guide Net in Front of the Condenser on the Performance of Automobile Air Conditioning System
...Show More Authors

 

The work of this paper is an investigation to improve the condenser performance of the automobile air conditioning system by enhancing the air-side heat transfer from the condenser through the use of an air guide net installed in front of the condenser face which is basically an aluminum plate having a circular entrance shape for the air passage.  The A/C system was examined under two types of test. The first test was conducted the air guide net, while the second was done with the air guide net. The performances of the A/C system under these tests were compared. For the second type of test, the experiment was carried out with three different size of air guide net, three different circular diameters (2, 3 and 3.5 cm) a

... Show More
View Publication Preview PDF
Crossref