Effect of Mixed Corrosion Inhibitors in Cooling Water System
...Show More Authors

The effect of mixed corrosion inhibitors in cooling system was evaluated by using carbon steel specimens and weight loss analysis. The carbon steel specimens immersed in mixture of sodium phosphate (Na2 HPO4) used as corrosion inhibitor and sodium glocunate (C6 H11 NaO7) as a scale dispersant at different concentrations (20,40, 60, 80 ppm) and at different temperature (25,50,75 and 100)ºC for (1-5) days. The corrosion inhibitors efficiency was calculated by using uninhibited and inhibited water to give 98.1%. The result of these investigations indicate that the corrosion rate decreases with the increase the corrosion inhibitors concentration at 80 ppm and at 100ºC for 5 days, (i.e, corrosion rate= 0.014gmd).    

 

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Sun Sep 30 2001
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Effect of Velocity and Temperature on Mass Transfer of Oxygen in Corrosion Processes
...Show More Authors

View Publication Preview PDF
Publication Date
Wed Dec 25 2019
Journal Name
International Journal Of Corrosion And Scale Inhibition
Evaluation and characterization of the symbiotic effect of benzylidene derivative with titanium dioxide nanoparticles on the inhibition of the chemical corrosion of mild steel
...Show More Authors

A new benzylidene derivative, namely N-benzylidene-5-phenyl-1,3,4-thiadiazol-2-amine (BPTA), has been synthesized and instrumentally confirmed with Elemental Analysis (CHN), Nuclear Magnetic Resonance (NMR), and Fourier Transform Infrared Spectroscopy (FT-IR). Titanium Dioxide (TiO2) nanoparticles (NPs) were synthesized and characterized by X-ray. The mutualistic complementary dependence of BPTA with TiO2 nanoparticles as anti-corrosive inhibitor on mild steel (MS) in 1.0 M hydrochloric acid has been tested at various concentrations and various temperatures. The methodological work was achieved by gravimetric measurement methods complemented with surface analysis. The synthesized inhibitor concentrations were 0.1 mM to 0.5 mM and the temper

... Show More
Preview PDF
Scopus (64)
Scopus
Publication Date
Tue Sep 30 2014
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Corrosion Inhibition of Mild Steel by Curcuma Extract in Petroleum Refinery Wastewater
...Show More Authors

The inhibitor property of curcuma longa L. extract in different concentrations of simulated refinery wastewater (0.05% - 2% wt) and at various temperatures (30, 35 and 40 ˚C) was investigated using weight loss method. The results showed that the presence of about 1.2 % (v/v) of curcuma extract gave about 84% inhibition indicating its effectiveness on mild steel corrosion in simulated refinery wastewater, besides the adsorption process on the mild steal surface obeyed the Langmuir adsorption isotherm.

View Publication Preview PDF
Publication Date
Sun Sep 30 2007
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Corrosion Inhibition of Aluminum Alloy in 50% Ethylene Glycol Solution
...Show More Authors

The present study was conducted to evaluate the effect of different inhibitors on the corrosion rate of aluminum in 50% (v/v) ethylene glycol solution at 80°C and pH 8.0 in which the electrochemical technique of linear sweep voltammetry was employed to characterize each inhibitor function and to calculate the corrosion rate from Tafel plots generated by a computer assisted  potentiostat.

It is found that both sodium dichromate and borax reduces the corrosion rate by polarizing the anodic polarization curve while sodium phosphate, potassium phosphate, and sodium benzoate reduces the corrosion rate by polarizing both the anodic and cathodic  polarization curve.

When inhibitor concentration increases from I g/l up

... Show More
View Publication Preview PDF
Publication Date
Fri Jan 01 2016
Journal Name
Journal Of Engineering
Thermal Characteristics of Closed Wet Cooling Tower Using Different Heat Exchanger Tubes Arrangement
...Show More Authors

This paper presents thermal characteristics analysis of a modified Closed Wet Cooling Tower (CWCT) based on heat and mass transfer principles to improve the performance of this tower in Iraq. A prototype of CWCT optimized by added packing was designed, manufactured and tested for cooling capacity of 9 kW. Experiments are conducted to explore the effects of various operational and conformational parameters on the thermal performance. In the test section, spray water temperature and both dry bulb temperature and relative humidity of the air measured at intermediate points of the heat exchanger and packing. Heat exchangers consist of four rows and eight columns for an inline tubes arrangement and six rows and five columns f

... Show More
View Publication Preview PDF
Publication Date
Fri Apr 01 2022
Journal Name
Baghdad Science Journal
Protection of Galvanized steel from corrosion in salt media using sulfur nanoparticles
...Show More Authors

                The characteristics of sulfur nanoparticles were studied by using atomic force microscope (AFM) analysis. The atomic force microscope (AFM) measurements showed that the average size of sulfur nanoparticles synthesized using thiosulfate sodium solution through the extract of cucurbita pepo extra was 93.62 nm. Protecting galvanized steel from corrosion in salt media was achieved by using sulfur nanoparticles in different temperatures. The obtained data of thermodynamic in the presence of sulfur nanoparticles referred to high value as compares to counterpart in the absence of sulfur nanoparticles, the high inhibition efficiency (%IE) and corrosion resistance were at high temperature, the corrosion rate or weig

... Show More
View Publication Preview PDF
Scopus (11)
Crossref (3)
Scopus Clarivate Crossref
Publication Date
Thu Dec 01 2011
Journal Name
Journal Of Economics And Administrative Sciences
Measurement of Impact of Banking System Development on Economic Growth in Iraq
...Show More Authors

At the heart of every robust economy is a vital banking system. The functional banking system can effectively perform several functions such as mobilizing savings, allocating credit, monitoring managers, transforming risks, and facilitating the financial transactions. This paper aims to measure the impact of banking system development on economic growth in Iraq. Credit to private sector divided by GDP used as a proxy of banking development. Real per capita GDP used as a proxy of economic growth. By using Autoregressive Distributed Lag (ARDL) model, the paper finds that the undeveloped Iraqi banking system could not promote economic growth in the country. Therefore, a variety of policies need to be taken to spur the role of bankin

... Show More
View Publication Preview PDF
Crossref
Publication Date
Sat Jul 22 2023
Journal Name
Journal Of Engineering
Experimental Investigation into the Heat and Mass Transfer in an Indirect Contact Closed Circuit Cooling Tower
...Show More Authors

The heat and mass transfer coefficients of the indirect contact closed circuit cooling tower, ICCCCT, were investigated experimentally. Different experiments were conducted involving the controlling parameters such as air velocity, spray water to air mass flow rate ratio, spray water flow rate, ambient air wet bulb temperature and the provided heat load to investigate their effects on the performance of the ICCCCT. Also the effect of using packing on the performance of the ICCCCT was investigated. It was noticed that these parameters affect the tower performance and the use of packing materials is a good approach to enhance the performance for different operational conditions. Correlations for mass and heat transfer coefficients are pres

... Show More
View Publication Preview PDF
Crossref
Publication Date
Fri Sep 30 2022
Journal Name
Industrial Engineering & Management Systems
Optimizing the Complex Systems Reliability Using Mixed Strategy in Ultra-fast Gas Turbine Protection System
...Show More Authors

View Publication
Crossref (1)
Scopus Clarivate Crossref
Publication Date
Sat Aug 01 2015
Journal Name
Journal Of Engineering
An Investigation into Thermal Performance of Closed Wet Cooling Tower for Use with Chilled Ceilings in Buildings
...Show More Authors

Chilled ceilings systems offer potential for overall capital savings. The main aim of the present research is to investigate the thermal performance of the indirect contact closed circuit cooling tower, ICCCCT used with chilled ceiling, to gain a deeper knowledge in this important field of engineering which has been traditionally used in various industrial & HVAC systems. To achieve this study, experimental work were implemented for the ICCCCT use with chilled ceiling. In this study the thermal performances of closed wet cooling tower use with chilled ceiling is experimentally and theoretically investigated. Different experimental tests were conducted by varying the controlling parameters to investigate their effects

... Show More
View Publication Preview PDF