Preferred Language
Articles
/
GBcKiI4BVTCNdQwCc0wn
Experimental study on thermo‐hydraulic performance of metal foam twisted tape in a double pipe heat exchanger
...Show More Authors
Abstract<p>A recent study compared experimentally the hydraulic and thermal activity of twisted tape inserts for two types, metal foam twisted tape (MFTT) and traditional twisted tape (TTT), in a double pipe heat exchanger. The investigation goal of the innovatively designed MFTT is to enhance the heat transfer process, which provides a higher thermal enhancement factor over those of TTT under the same conditions. Heat transfer activity in terms of Nusselt number (<italic>Nu</italic>) and Nusselt number ratio (<italic>Nu</italic>/<italic>Nu</italic><sub>o</sub>) as the heat exchanger equipped with the proposed MFTT and TTT inserts with various tape‐twist ratios (<italic>y</italic>/<italic>W</italic> = 3.6, 5.2, and 6.8) are considered over various values of Reynolds numbers (16,300 < <italic>Re</italic> < 32,500). The results reveal an improvement in heat transfer rate with both MFTT and TTT and this improvement is proportional inversely to the twisted ratio, but the MFTT showed the highest value of heat transfer compared to TTT and clear tube. Also, the <italic>Nu</italic> of MFTT augments averaged about 175%–230% compared to the TTT depending on the twist ratio and about 275% and 500% over that of the clear tube. At a twist ratio of 3.6, the heat transfer coefficient is recorded at 37% and 45% for MFTT and TTT models, respectively, with an increase in Re. However, friction factor (<italic>f</italic>) increases about 35% for MFTT with decreasing in twist ratio (from 6.8 to 3.6). The effectiveness of the proposed MFTT in the range of <italic>Re</italic> used is found to be about 12%, 15%, and 18% higher than those induced by TTT at twisted tape ratio (<italic>y</italic>/<italic>w</italic> = 3.6, 5.2, and 6.8), respectively.</p>
Scopus Clarivate Crossref
View Publication
Publication Date
Fri Sep 02 2022
Journal Name
Frontiers In Built Environment
Thermal analysis of horizontal earth-air heat exchangers in a subtropical climate: An experimental study
...Show More Authors

The earth-air heat exchanger (EHX) has a promising potential to passively save the energy consumption of traditional air conditioning systems while maintaining a high degree of indoor comfort. The use of EHX systems for air conditioning in commercial and industrial settings offers several environmental benefits and is capable of operating in both standalone and hybrid modes. This study tests the performance and effectiveness of an EHX design in a sandy soil area in Baghdad, Iraq. The area has a climate of the subtropical semi-humid type. Ambient air temperatures and soil temperatures were recorded throughout the months of 2021. During the months of January and June, the temperatures of the inlet and outflow air at varying air veloci

... Show More
View Publication
Scopus (7)
Crossref (5)
Scopus Clarivate Crossref
Publication Date
Thu May 18 2023
Journal Name
Journal Of Engineering
Experimental Study of Power Increase Transient in Heat Generation Systems Simulated By Immersed Heat Source
...Show More Authors

Theoretical and experimental investigations of the transient heat transfer parameters of constant heat flux source subjected to water flowing in the downward direction in closed channel are conducted. The power increase transient is ensured by step change increase in the heat source power. The theoretical investigation involved a mathematical modeling for axially symmetric, simultaneously developing laminar water flow in a vertical annulus. The mathematical model is based on one dimensional downward flow. The boundary conditions of the studied case are based on adiabatic outer wall, while the inner wall is subjected to a constant heat flux. The heat & mass balance equation derived for specified element of bulk water within the annulu

... Show More
View Publication Preview PDF
Crossref
Publication Date
Tue Oct 01 2019
Journal Name
Journal Of Engineering
Hydraulic Analysis and Performance Evaluation of Combined Trunk Sewers: a Case Study of Baghdad City.
...Show More Authors

Sewer system plays an essential task in urban cities by protecting public health and the environment. The operation, maintenance, and rehabilitation of this network have to be sustainable and scientifically. For this purpose, it is crucial to support operators, decision makers and municipalities with performance evaluation procedure that is based on operational factors. In this paper, serviceability and performance indicator (PI) principles are employed to propose methodology comprising two enhanced PI curves that can be used to evaluate the individual sewers depending on operational factors such as flowing velocity and wastewater level in the sewers. To test this methodology; a case study of al-Rusafa in Baghdad city is

... Show More
View Publication Preview PDF
Crossref
Publication Date
Thu Feb 28 2019
Journal Name
Journal Of Engineering
Hydraulic Analysis and Performance Evaluation of Combined Trunk Sewers: A Case Study of Baghdad City.
...Show More Authors

Sewer system plays an indispensable task in urban cities by protecting public health and the environment. The operation, maintenance, and rehabilitation of this network have to be in a sustainable and scientific manner. For this purpose, it is important to support operators, decision makers and municipalities with performance evaluation procedure that is based on operational factors. In this paper, serviceability and performance indicator (PI) principles are employed to propose methodology comprising two enhanced PI curves that can be used to evaluate the individual sewers depending on operational factors such as flowing velocity and wastewater level in the sewers. In order to test this methodology; a case study of al-Ru

... Show More
View Publication Preview PDF
Crossref
Publication Date
Sun Nov 01 2015
Journal Name
Journal Of Engineering
Experimental Evaluation of Thermal Performance of Solar Assisted Vapor Compression Heat Pump
...Show More Authors

The thermal performance of indirect expansion solar assisted heat pump, IX-SAHP, was investigated experimentally under Iraqi climate. An Indirect-Solar Assisted Heat Pump system was designed, built, instrumented and tested. Experimental tests were conducted by varying the controlling parameters to investigate their effects on the thermal performance of the IX-SAHP such as cooling water flow rate, heating water flow rate, ambient temperature and solar radiation intensity. The investigation covered values of cooling water flow rate of (2, 3, 4, 5 l/min) and heating water flow rate of (2, 3, 4, 5 l/min) under meteorological condition of Baghdad from November 2014 to January 2015.

The results indicated that the performance of the IX-

... Show More
View Publication Preview PDF
Publication Date
Wed Jul 31 2019
Journal Name
Journal Of Engineering
Enhancing Heat Transfer in Tube Heat Exchanger by Inserting Discrete Twisting Tapes with Different Positions
...Show More Authors

Enhancement of heat transfer in the tube heat exchanger is studied experimentally by using discrete twisted tapes. Three different positions were selected for inserting turbulators along tube section (horizontal position by α= 00, inclined position by α= 45 0 and vertical position by α= 900). The space between turbulators was fixed by distributing 5 pieces of these turbulators with pitch ratio    PR = (0.44). Also, the factor of constant heat flux was applied as a boundary condition around the tube test section for all experiments of this investigation, while the flow rates were selected as a variable factor (Reynolds number values vary from 5000 to 15000). The results s

... Show More
View Publication Preview PDF
Crossref (1)
Crossref
Publication Date
Thu Jan 31 2019
Journal Name
Journal Of Engineering
Experimental Study on Double-Pass Solar Air Heater with and without using Phase Change Material
...Show More Authors

In this paper, an experimental study was conducted to enhance the thermal performance of a double-pass solar air heater (SAH) using phase change material (PCM) for thermal storage at climatic conditions of Baghdad city - Iraq. The double-pass solar air heater integrated with thermal storage system was manufactured and tested to ensure that the air heating reserved after the absence of the sun. The rectangular cavity filled with paraffin wax was used as a latent heat storage and incorporated into the lower channel of solar air heater. Experiments were carried out to evaluate the charging and discharging characteristics of two similar designed solar air collectors with and without using phase change material at a constant

... Show More
View Publication Preview PDF
Crossref (20)
Crossref
Publication Date
Thu Jul 01 2021
Journal Name
Applied Thermal Engineering
Consecutive charging and discharging of a PCM-based plate heat exchanger with zigzag configuration
...Show More Authors

View Publication
Scopus (60)
Crossref (53)
Scopus Clarivate Crossref
Publication Date
Fri Apr 01 2022
Journal Name
Journal Of Engineering
Numerical study of natural convection in an annulus between two concentric cylinders provided with metal foam fins
...Show More Authors

Natural convection in an annular space provided with metal foam fins attached to the inner cylinder is studied numerically. The metal foam fins made of copper were inserted in different axial sections with three fins in each section. The temperature of the inner cylinder is kept constant while the annular outer surface is adiabatic. The thickness effect of the inner pipe wall was considered. Naiver Stokes equation with Boussinesq approximation is used for the fluid regime while Brinkman-Forchheimer Darcy model is used for metal foam. In addition, the local thermal non-equilibrium condition in the energy equation of the porous media is presumed. The effect of Rayleigh numb

... Show More
View Publication Preview PDF
Crossref
Publication Date
Sun Dec 30 2007
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Prevention of Scale Formation in Heat Exchanger Pipes by Using Magnetic Field
...Show More Authors

The possibility of using the magnetic field technique in prevention of forming scales in heat exchangers pipes using
hard water in heat transfer processes, also the studying the effective and controllable parameters on the mechanism of
scale formation.
The new designed heat exchanger experimental system was used after carrying out the basic process designs of the
system. This system was used to study the effect of the temperature (40-90 °C) and water flow rate (0.6-1.2 L/min) on
the total hardness with time as a function of precipitation of hardness salts from water and scale formation.
Different magnetic field designs in the heat exchanger experimental system were used to study the effect of magnetic
field design a

... Show More
View Publication Preview PDF