Cooling Load Calculations For Typical Iraqi Roof And Wall Constructions Using Ashrae's RTS Method
...Show More Authors

The present work is an attempt to develop design data for an Iraqi roof and wall constructions using the latest ASHRAE Radiant Time Series (RTS) cooling load calculation method. The work involves calculation of cooling load theoretically by introducing the design data for Iraq, and verifies the results experimentally by field measurements. Technical specifications of Iraqi construction materials are used to derive the conduction time factors that needed in RTS method calculations. Special software published by Oklahoma state university is used to extract the conduction factors according to the technical specifications of Iraqi construction materials.  Good agreement between the average theoretical and measured cooling load is obtained and the difference between them does not exceed 9.3%.

 

 

View Publication Preview PDF
Quick Preview PDF
Publication Date
Tue Sep 01 2015
Journal Name
Journal Of Engineering
Internal Convective Heat Transfer Effect on Iraqi Building Construction Cooling Load
...Show More Authors

This work involves the calculation of the cooling load in Iraqi building constructions taking in account the effect of the convective heat transfer inside the buildings. ASHRAE assumptions are compared with the Fisher and Pedersen model of estimation of internal convective heat transfer coefficient when the high rate of ventilation from ceiling inlet configuration is used. Theoretical calculation of cooling load using the Radiant Time Series Method (RTSM) is implemented on the actual tested spaces. Also the theoretical calculated cooling loads are experimentally compared by measuring the cooling load in these tested spaces. The comparison appears that using the modified Fisher and Pedersen model when large ventilation ra

... Show More
View Publication Preview PDF
Publication Date
Thu Mar 31 2016
Journal Name
Iraqi Journal Of Chemical And Petroleum Engineering
Load Effect on Wall Attachment Fluidics Amplifier Performance
...Show More Authors

An experimental work has been conducted on wall attachment fluidics amplifiers, one of them to study the effect of output pressure or load on the amplifier performance. The output load has been simulated as a piston connected to the device output and the piston can be loaded accordingly. The results shows that the output volume flow rate increases as the supply pressure increases under different load and the output pressure remains constant as the supply pressure increases under constant load.

View Publication Preview PDF
Publication Date
Sat Dec 01 2018
Journal Name
Al-khwarizmi Engineering Journal
Crack Growth Behavior through Wall Pipes under Impact Load and Hygrothremal Environment
...Show More Authors

This research concerns study the crack growth in the wall of pipes made of low carbon steel under the impact load and using the effect of hygrothermal (rate of moisture 50% and 50℃ temperature). The environmental conditions were controlled using high accuracy digital control with sensors. The pipe have a crack already. The test was performed and on two type of specimens, one have length of 100cm and other have length 50cm. The results were, when the humidity was applied to the pipe, the crack would enhance to growth (i.e. the number of cycles needed to growth the crack will reduce). In addition, when the temperature was increase the number of cycles needed to growth the crack are reduced because the effect of heat on the mechanical pro

... Show More
View Publication Preview PDF
Crossref
Publication Date
Wed Mar 01 2023
Journal Name
Journal Of Engineering
Effect of a Parked Car Orientation on a Temperature Distribution and Cooling Load Calculation: Experimental Study
...Show More Authors

When a vehicle is left parked in the sun for an extended period, the gathered heat causes damage to several interiors within the cabin and causes discomfort for people and animals left inside the car. In the present work, the effect of the orientation of a parked white minibus on temperature distribution and cooling load calculation is studied experimentally in an open environment. Two different cases were studied facing south and facing east. For several hours, the temperature inside the car cabin had been monitored and measured at five separate locations. The cooling load calculations are carried out based on the experimental measurements. The results show that the overheating of parked cars always happens as a result

... Show More
View Publication Preview PDF
Crossref (2)
Crossref
Publication Date
Thu Jan 01 2015
Journal Name
Journal Of Engineering
Experimental Study of the effect of closed cavity wall on buildings cooling loads saving
...Show More Authors

The experimental study showed the use of closed cavity wall (the thickness of the cavity 5cm) made a percentage reduction in the cooling load caused by heat gain from the wall by (21.5 %) compared with the conventional wall. also the thermal resistance of the closed cavity was an average (0.2 m2.oC/W).

The experimental results of the study showed that the use of closed cavity wall reduced the average temperature of the inner surface of the wall during the day, and that the reduction was an average (0.45 oC)  when compared with the conventional wall , as well as the use of closed cavity wall reduced the temperature difference range of the inner surface of the wall during the day, and that the

... Show More
View Publication
Publication Date
Fri Jan 01 2016
Journal Name
Journal Of Engineering
A Mathematical Model of a Thermally Activated Roof (TAR) Cooling System Using a Simplified RC-Thermal Model with Time Dependent Supply Water Temperature
...Show More Authors

This paper presents a computer simulation model of a thermally activated roof (TAR) to cool a room using cool water from a wet cooling tower. Modeling was achieved using a simplified 1-D resistance-capacitance thermal network (RC model) for an infinite slab. Heat transfer from the cooling pipe network was treated as 2-D heat flow. Only a limited number of nodes were required to obtain reliable results. The use of 6th order RC-thermal model produced a set of ordinary differential equations that were solved using MATLAB - R2012a. The computer program was written to cover all possible initial conditions, material properties, TAR system geometry and hourly solar radiation. The cool water supply was considered time

... Show More
View Publication Preview PDF
Publication Date
Fri Feb 05 2021
Journal Name
Research In Intelligent And Computing In Engineering
Implementing Web Testing System Depending on Performance Testing Using Load Testing Method.
...Show More Authors

Web testing is very important method for users and developers because it gives the ability to detect errors in applications and check their quality to perform services to users performance abilities, user interface, security and other different types of web testing that may occur in web application. This paper focuses on a major branch of the performance testing, which is called the load testing. Load testing depends on an important elements called request time and response time. From these elements, it can be decided if the performance time of a web application is good or not. In the experimental results, the load testing applied on the website (http://ihcoedu.uobaghdad.edu.iq) the main home page and all the science departments pages. In t

... Show More
Publication Date
Mon Jan 01 2018
Journal Name
International Journal Of Science And Research (ijsr)
Height-to-Length Ratio Effect on the Response of Unreinforced Masonry Wall Subjected to Vertical Load Using Detailed-Micro Modeling Approach
...Show More Authors

This paper aimed to investigate the effect of the height-to-length ratio of unreinforced masonry (URM) walls when loaded by a vertical load. The finite element (FE) method was implemented for modeling and analysis of URM wall. In this paper, ABAQUS, FE software with implicit solver was used to model and analysis URM walls subjected to a vertical load. In order to ensure the validity of Detailed Micro Model (DMM) in predicting the behavior of URM walls under vertical load, the results of the proposed model are compared with experimental results. Load-displacement relationship of the proposed numerical model is found of a good agreement with that of the published experimental results. Evidence shows that load-displacement curve obtained fro

... Show More
Publication Date
Sat Feb 01 2020
Journal Name
Physics Of Fluids
Modeling the effects of slip on dipole–wall collision problems using a lattice Boltzmann equation method
...Show More Authors

We study the physics of flow due to the interaction between a viscous dipole and boundaries that permit slip. This includes partial and free slip, and interactions near corners. The problem is investigated by using a two relaxation time lattice Boltzmann equation with moment-based boundary conditions. Navier-slip conditions, which involve gradients of the velocity, are formulated and applied locally. The implementation of free-slip conditions with the moment-based approach is discussed. Collision angles of 0°, 30°, and 45° are investigated. Stable simulations are shown for Reynolds numbers between 625 and 10 000 and various slip lengths. Vorticity generation on the wall is shown to be affected by slip length, angle of incidence,

... Show More
View Publication
Scopus (13)
Crossref (12)
Scopus Clarivate Crossref
Publication Date
Thu Jun 08 2017
Journal Name
Ibn Al-haitham Journal For Pure And Applied Sciences
Theoretical Calculations of the Electron Transport Parameters in CH4-Ar and CH4-Ne Mixtures Gases Using Monte Carlo Method
...Show More Authors

    The result of concentration varying of mixture methane with argon and neon gas are believed to study the change in electrons energy distribution function and then the change of the electrons transport parameters including the drift velocity, the mean energy, characteristics energy and diffusion coefficient. In the present work,a contemporary developed computer, simulation program known as Bolsig+ is being used for calculating the electron transport parameters.
 