The chlorine concentration variation in Baghdad water networks was studied. The
chlorine data were collected from Mayoralty of Baghdad and Ministry of Environment
(MOE) for the networks for both sides of the city Karkh and Rasafa for (2008-2009). The
study of these data indicates that there are no systematic testing program .Classified GIS
maps showed that the areas far from the treatment plants have almost always low
chlorine concentration .This indicates that the problem of the low chlorine concentration
in the far areas is due to cracks of pipe along the conveyance path ,as expected. The area's
most frequently have low concentration are Al-sadir,Al-Kadhimya, and Al-Amiria . It
was found also that the chlorine concentrations were lowest in summer months than those
in winter months.The Amiria area district (636) was selected as a case study to test the
ability of using the quantitative- qualitative model in the EPANET software, to find the
required onsite chlorine injection point number, locations and dose, so as to raise the
chlorine concentration to the acceptable limits in the other nodes of the network. The
bulk decay coefficient was found to be (-2.212)1/day and the wall coefficients were
found to be between (-0.001)to(-0.9)1/day The main conclusion of this study is that the
onsite injection can improve the chlorine concentration in Baghdad water supply
networks. The EPANET model can be used effectively to obtain the required injection
program for this purpose.
Chlorine disinfection is a globally used method to ensure the safety of drinking water. However, it has not always been successful against viruses and, therefore, it is important to find new methods to disinfect water. Seventeen different coliphages were isolated from the treated municipal wastewater. These coliphages and MS2 were treated with different dosages of chlorine in drinking water, and a combined chlorine/ultraviolet irradiation treatment for the chlorine-resistant coliphages. Chlorine disinfection with 0.3–0.5 mg/L total chlorine (free Cl-dosage 0.12–0.21 mg/L) for 10 min achieved 2.5–5.7 Log10-reductions for 11 sensitive coliphages. The six most resistant coliphages showed no reduction with these chlorine concentra
... Show MoreThe approach of the research is to simulate residual chlorine decay through potable water distribution networks of Gukookcity. EPANET software was used for estimating and predicting chlorine concentration at different water network points . Data requiredas program inputs (pipe properties) were taken from the Baghdad Municipality, factors that affect residual chlorine concentrationincluding (pH ,Temperature, pressure ,flow rate) were measured .Twenty five samples were tested from November 2016 to July 2017.The residual chlorine values varied between ( 0.2-2mg/L) , and pH values varied between (7.6 -8.2) and the pressure was very weak inthis region. Statistical analyses were used to evaluated errors. The calculated concentrations by the calib
... Show MoreThis study was done to examine the concentration of residual chlorine from different regions at AL Risafa side. The samples were collected from Baghdad AL- Jadida, Shareaa Phlistain, AL- Shaab and AL- Habibea, Al-Karrada, Al-Jadria, Al-Adamia at April-August/2013 .The Electrical Conductivity (Ec) and total dissolve solid (TDS), hang about its normal rate according to (WHO) but the Turbidity go beyond it’s limit to reach (11NTU) where the highest peak was recorded in Baghdad AL Jadida. The results show that chlorine concentration were decreased in the August compared with April because of high Temperature, and long in sun shine duration. It is found that there is inverse proportionality between residual chlorine and temperature. Same tr
... Show MoreAbstract To ensure that the distribution system has safe drinking water. It is necessary to know the residual chlorine concentrations at various points in the network. A chlorine photometer device was used to measure twenty points taken every day for a week at a selected time in the distribution system. Both pressures and flows in the network were measured using bourdon gauge and Tuf-2000H Handheld Digital ultrasonic flow meters. WaterGEMS CONNECT Edition update one software was used to simulate the flow in the network. The Baghdad water department provided the data about the network, such as the lengths of pipes, the layout of the network, and pipes diameters. The network calibrated consists of 781 pipes of different lengths and 542 juncti
... Show MoreChlorine doped SnS have been prepared utilizing chemical spray pyrolysis. The effects of chlorine concentration on the optical constants were studied. It was seen that the transmittance decreased with doping, while reflectance, refractive index, extinction coefficient, real and imaginary parts of dielectric constant were increased as the doping percentage increased. The results show also that the skin depth decrease as the chlorine percentage increased which could be assure that it is transmittance related.
This study was aimed to investigat integrated system for in vitro growth of paulownia plants by assessing the efficacy of chlorine dioxide (ClO2) as an alternative to autoclave in sterilizing culture medium. Therefore, this study was devised to compare autoclave sterilization at three different times (5, 10, and 15) minutes and three different concentrations of ClO2 (0, 0.4, 0,8, 1) mg/L. The results showed that, compared with (0.4) mg/L concentration, concentrations of (0.8 and 1) mg/L are more effective at sterilizing the culture medium. ClO2 sterilization improved individual single node growth more than autoclave sterilization. Since ClO2 is non-toxic, it could be used as a safe alternative to autoclave when propagating paulown
... Show MoreThe impact of decorating Fe, Ru, Rh, and Ir metals upon the sensing capability of a gallium nitride nanotube (GaNNT) in detecting chlorine trifluoride (CT) was scrutinized using the density functionals B3LYP and B97D. The interaction of the pristine GaNNT with CT was a physical adsorption with the sensing response (SR) of approximately 6.9. After decorating the above-mentioned metals on the GaNNT, adsorption energy of CT changed from −5.8 to −18.6, −18.9, −19.4, and −20.1 kcal/mol by decorating the Fe, Ru, Rh, and Ir metals into the GaNNT surface, respectively. Also, the corresponding SR dramatically increased to 39.6, 52.3, 63.8, and 106.6. This shows that the sensitivity of the metal-decorated GaNNT (metal@GaNNT) increased by in
... Show MoreAbstract. In this research, the uranium concentration in (16) water samples collected from some agricultural areas surrounded with AlTuwitha nuclear site in Baghdad-Iraq was measured by using a CR-39 detector. The concentration of uranium in this study was from (0.6 ± 0.33mg/l) to (2.51 ± 0.49 mg/l), and the weighted average for the concentrations (1.262 ± 0.402 mg/l). The results showed it is a concentration of uranium level in water samples studied is higher than the allowed limit recommended by WHO and ICRP.
In the present study ten samples of bottled water from Baghdad conservative were taken to measure the concentration of radon gas by using nuclear track detector LR-115.The result obtained are varying from(0.033)to(0.007)pCi.l-1and these values are very low than the allowed limits (5) pCi.l-1, and specific activity from bottled water has been calculated which was vary from (0.00027)to(0.00126) Bq.l-1 and these values are very low than allowed limits (0.0123) Bq.l-1 that mean the bottled water was treated with good treatment to decrease the side effect of radon